7.2   Fault Explanation - Probable Cause - Solution 
 
Fault 
Code / 
# 
LED 
Fault # or 
Code 
Description 
 
Explanation: Probable Cause: Solution 
Fn List 
Ref 
 
nFLA 
None 
 
No Full Load Amps 
Motor nameplate Full Load Amps (FLA) was not entered by the 
user. Starter will not operate without this information. See section 
3.1. 
 
F001 
 
rSt 
None Reset 
Reset of fault condition is successful. The starter is ready for the 
next Start command. 
 
N/A 
 
Inh 
 
None 
Inhibited 
ttempted action is not possible. Probable cause: 
1) The starter is in the Run mode. The starter must be in the 
Stopped mode before changes can be entered. 
2) The parameter that is being entered has been locked out with 
the Customer Password. See section 5.5.11 for details. 
 
 
N/A 
FLt ??? Multiple Faults 
Indicates the rare occurrence of multiple simultaneous faults. The 
LEDs associated with those faults should illuminate. 
 
N/A 
CdLo  None  Coast Down Lock Out 
The Coast Down Lock Out timer has been enabled by the user 
and the time has not yet expired when a Start command is given. 
See section 5.5.8 for details. 
 
F048 
SHLo  None  Start per Hour Lock Out 
The Starts per Hour Lock Out timer has been enabled by the 
user, and the time has not yet expired when a Start command is 
given. See section 5.5.8 for details. 
 
F049 
tSLo  None  Time between Starts Lock Out 
The Time Between Starts Lock Out timer has been enabled by 
the user, and the time has not yet expired when a Start command 
is given. See section 5.5.8 for details. 
 
F50 
Loc  None  Lock Out Timer engaged 
ny one of the above Lock Out Protection features is preventing 
operation until the timer expires. See section 5.5.8 for additional 
details. Remaining time values are located at F055 - F059. 
F048 - F050
PASS  None  Successful password entry 
Customer password was entered and accepted. Parameter lock 
is now released. All user functions can be accessed. 
F070 ā F072
Err None 
 
Password entry Error 
The password that you are trying to enter is invalid. Check with 
authorized user personnel for password information. 
 
Any 
End None 
 
Successful parameter change 
The data or setpoint entered into a Function has been accepted 
and stored into memory as the new value. 
 
All 
dFLt None 
 
Default 
Parameters have been successfully returned to the Factory 
Default settings. 
 
F071 
triP None 
 
Tripped 
Control power was cycled and the Start command given while the 
starter was in a tripped condition. The existing fault condition will 
display after the Start command is removed. 
 
N/A 
HXXX None 
 
Remaining Thermal Capacity 
(XXX will show number value 
from 000 to 100) 
Thermal capacity remaining in the motor. As this number counts 
down toward zero, the motor is approaching an overload 
condition. After Overload Trip occurs, this number will increase 
back toward 100% as the motor cools. The value at which an 
Overload Trip can be reset will dynamically changes as the TE 
starter learns the amount of Thermal capacity that is used on 
successful start attempts. Required Thermal Capacity to start  
can be displayed in F059. 
F001-F004, 
F059 
CLr None 
 
Retentive memory has been 
Cleared 
 
fter entering a value of "2" into F071, the Thermal Register and 
all Lock Out Timer values will be cleared (reset to 0). Use this 
function only for emergency restart. Motor damage may result. 
F071 
 