Basi
 
nsta
at
on and Operat
on G
de
T
Ser
es D
ta
olid
tate 
o
t 
tarters 1
1250A
 
51 | Page 
 
 
 
5.6.8.a (continued) Function 51: Internal Protection Features 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
  Note:  
To restore all settings back to the factory default, enter a value of 
127. A value other than the default value of 127 indicates that one or 
more functions have been changed. To determine which of the 
protective functions have been changed/turned-off subtract the value 
displayed from 127 and compare the result against the ‘decimal 
value’ column shown in table 5.6.8.a. 
 
Example: F051 reads a value of 109.Subtract109 from 127 and a value 
of 18 remains. The value 18 does not represent a single bit value 
indicating that more than one function has been changed. 
Referring to Table 5.6.8.a, find the largest decimal value as shown in 
the ‘decimal value’ column smaller than 18. In this case, it’s a value 
of 16 (bit 4). This leaves a value of 2 (18 minus 16) which represents 
bit 1 (2). So in this example a value of 109 indicates that the Shunt 
Trip feature had been turned off (bit 4), and the Expected Phase 
Sequence had been changed to A-C-B (bit 1). 
 
Instead of determining the previous selection add up all values in 
‘decimal value’ column of the functions to be turned off and subtract 
this value from 127 and program the result into F051.  
 
Bit 
# 
Fault 
Display 
Code 
Protection 
Function 
Description 
Default 
Bit 
Setting 
Decimal 
Value 
0 ROT* 
Phase 
Rotation 
Trip 
Phase Rotation protection.  
Phase rotation must match selection in Bit #2 
below. Setting to Off (0) will make the TE 
insensitive for use behind a reversing contactor 
0 (Off)  1  
1 ABC 
Expected 
Phase 
Sequence 
2 = A-B-C Phase Rotation Sequence Only 
0 = A-C-B Phase Rotation Sequence Only 
1  
(A-B-C 
Rotation) 
2 
2 
PLa or 
PLc* 
Phase 
Current  
Loss 
Phase Current Loss, any phase current reading 
that is less than 12% of the CT rating after 3 
seconds from Start command. 
1 (On)  4 
3 SS* 
Shorted 
SCR 
At least one SCR is shorted; There is no voltage 
drop across the SCR phase assembly. 
1 (On)  8 
4 ST* 
Shunt  
Trip 
Shunt Trip of the main Circuit Breaker or Isolation 
Contactor (if provided and wired to an Aux. relay 
in F060-F061). Two or more SCRs have shorted 
in opposing phases so current is flowing to the 
motor while the TE was in the Off state. 
1 (On)  16 
5 PTc* 
PTC Input 
Trip 
PTC Trip function. This can be disabled so that a 
jumper is not required across the PTC inputs. 
1 (On)  32 
6 
PLd or 
n3Ph 
Line Phase 
Loss Trip 
Protection against loss of input line voltage. 
Disable when using an In-Line Isolation Contactor 
or any other system that normally removes line 
power from the starter. Resets automatically when 
line voltage returns. 
1 (On) 
64 
7  ---  Reserved  Reserved for factory use  0 (Off)  128 
* = Operating Mode designation. See Fault Code List for description. 
Table 5.6.8.a:  Function 51 table of Hardware Protection Features 
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com