EasyManua.ls Logo

Toshiba TE Series - 5.6.12.b Statistical Data

Toshiba TE Series
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Basi
c
I
nsta
l
l
at
i
on and Operat
i
on G
u
i
de
T
E
Ser
i
es D
i
i
ta
l
S
olid
S
tate
S
o
f
t
S
tarters 1
8
1250A
59 | Page
5.6.12.b Statistical Data
F094 - F097 display information from the Run Time / Elapsed Time
meter and Run-Cycle counter.
Run Time includes Accel, Run, Decel, and Jog operations.
Run Cycles are counted only when the starter reaches At-Speed
mode.
F094 = Run Time, Hours
Factory Setting = 0000
Range = 000.9 - 999.9 hours
Run times in excess of 999.9 are recorded in F095.
F095 = Run Time, K Hours
Factory Setting = 0000
Range = 0000 - 9999 K hours
0001 in readout means a run time of 1,000 hours.
F096 = Run Counts
Factory Setting = 0000
Range = 0000 – 9999
Run counts in excess of 9999 are recorded in F097.
F097 = Run Counts, 10K Times
Factory Setting = 0000
Range = 0000 - 9999, 10 thousand times
0001 in readout means a run count of 10,000 operations.
Examples:
Overflow
Value
Basic
Value
Run Time
23,047 Hours
F095 F094
0002 3047
Run Counts
18,702 Starts
F097 F096
0001 8702
Table 5.5.15: Statistical Data Examples
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Other manuals for Toshiba TE Series

Related product manuals