Basi
nsta
at
on and Operat
on G
de
T
Ser
es D
ta
olid
tate
o
t
tarters 1
1250A
59 | Page
5.6.12.b Statistical Data
F094 - F097 display information from the Run Time / Elapsed Time
meter and Run-Cycle counter.
Run Time includes Accel, Run, Decel, and Jog operations.
Run Cycles are counted only when the starter reaches At-Speed
mode.
F094 = Run Time, Hours
Factory Setting = 0000
Range = 000.9 - 999.9 hours
Run times in excess of 999.9 are recorded in F095.
F095 = Run Time, K Hours
Factory Setting = 0000
Range = 0000 - 9999 K hours
0001 in readout means a run time of 1,000 hours.
F096 = Run Counts
Factory Setting = 0000
Range = 0000 – 9999
Run counts in excess of 9999 are recorded in F097.
F097 = Run Counts, 10K Times
Factory Setting = 0000
Range = 0000 - 9999, 10 thousand times
0001 in readout means a run count of 10,000 operations.
Examples:
Overflow
Value
Basic
Value
Run Time
23,047 Hours
F095 F094
0002 3047
Run Counts
18,702 Starts
F097 F096
0001 8702
Table 5.5.15: Statistical Data Examples
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com