INTERFACE MANUAL 
  The dummy connector can be removed while the POWER switch is set ON or OFF.   
If the dummy connector is removed while the servo power is turned on, however, the 
servo power is turned off automatically.    (While the dummy connector or teach 
pendant is not connected, safety measures are effected to prevent the servo power 
from actuating.) 
  The TP disconnect switch is provided on the lower left side of the TP connector 
(when seen from the controller front side).    When the dummy connector or teach 
pendant connector is disconnected while pressing this switch, the controller servo 
power remains on.    Change the connector while pressing the TP disconnect switch 
continuously. 
  If the TP disconnect switch is kept pressed for long hours, however, the safety 
device works to turn off the servo power (i.e., emergency stop contact output is ON).   
The time for attaching or detaching the connector should be ninety (90) seconds or 
less. 
 
 
!
 
CAUTION
 
Unless the TP cable or dummy connector is connected 
with the TP connector of the TS2000/TS2100 robot 
controller, the servo power cannot be turned on. 
 
 
!
 
CAUTION
 
NEVER keep pressing the TP disconnect switch 
intentionally. 
 
  As shown in Fig. 6.1, the teach pendant I/O signals include the I/O signals for data 
transmission between the teach pendant and controller, signals for identifying servo 
ON, emergency stop and enable input from the teach pedant, and P24V and P24G 
signals for supplying the power to the teach pendant. 
  Data transmission between the teach pendant and TS2000/TS2100 robot controller 
is performed in the current loop system. 
These I/O signals are used exclusively for the TP1000 teach pendant, and cannot be 
used for any other equipment. 
While the teach pendant is disconnected, processing of emergency stop is effective 
and the servo power cannot be turned on.    Unless the teach pendant is used, use 
the attached jumper connector (D-SUB 15 pin). 
 