Pending Genstart, Cranking Genset, and AC Available
Starter Cooldown Gen Won’t Start
Gen Quiet Fault
These messages will be displayed whenever the RC7GS has been setup to start the
generator at a specified condition, and that condition has arisen.
When the initiating condition (SOC or battery voltage) has occurred, the ‘ ’
message will be displayed for approximately two minutes awaiting a change in the condition
or a manual override. If neither occurs, the RC7GS will attempt to start the generator and
will display the ’ ‘ message.
When the generator starts, there will be a brief delay to allow the genset to reach operating
speed and allow to synchronize voltage with it; then the ’ ‘
message will be displayed.
In the event the genset does not start within thirty-seconds, a two-minute starter cool-down
period will occur and the ’ ‘ message will be displayed after which another
attempt to start the genset will occur. This cycle (cranking - cooldown - cranking) will repeat
three more times for a total of four attempts to start the genset over a 12-minute period.
If the genset has not started after four attempts, the RC7GS will display the ’
“ error message and the Error LED on the faceplate will be lighted red. No further
attempts to start the genset will occur. Correct the generator starting problem and manually
start the genset. You can reset it using the Setup menu
.
Whenever the RC7GS Gen Start function is configured to Auto Start your generator under a
specified condition and that condition occurs during the specified Gen Quiet period, the
LCD will display the Gen Quiet Fault message, the Error LED will be lighted, and the remote
control unit will emit a series of beeping sounds for up to five minutes or until the error
condition is corrected (whichever occurs first). You can override the Gen Quiet period by
resetting the Gen Quiet Begin and End time to 00:00. If the genset is manually started
during the quiet time, it will be shut down automatically.
Pending Genstart
Cranking Genset
AC Available
Starter Cooldown
Gen Won‘t
Start
and
the inverter/charger
by changing the GenStart option to
’Manual,‘
The Gen Quiet Fault error is reset automatically at the end of the quiet time if no other
action is taken, and the Auto Genstart function will execute.
Genset Status:
AC Available
Genset Status:
Cranking Genset
Genset Status:
PendingGenstart
Genset Status:
Starter Cooldown
Genset Status:
Gen Wont start
System Status:
Gen Quiet Fault
System Status:
Waiting for AC
10
Copyright Trace Engineering Co. Inc. Tel (360) 435-8826 Part Number 822-4
5916 195 Street, NE Fax (360)435-2229 Effective: November 1, 1997
Arlington, WA 98223 USA www.traceengineering.com Page
th