12
Default = Disable
Select = Return water
Zone
Outdoor air
[TYPE]
Return water
Default = 50%
Range = 10% to 120%
Zone
Default = 100%
Range = 50% to 300%
Outdoor
Default = 10%
Range = -80% to 80%
[TYPE]
Return:
Default = 2,7°C
Range = 0° to 11°C
Zone
Default = 25°C
Range = 10 to 55°C
Outdoor
Default = 32°C
Range = 10 to 55°C
[TYPE]
Return water
Default = 2,7°C
Range = 0° to 11°C
Zone
Default = -15°C
Range = 0° to 11°C
Outdoor
Default = 2,7°C
Range = 0° to 11°C
Default = Disable
Default = -3°C
Select = -7 to -1°C
Chilled water reset type [TYPE]
Press (+) (-) to change setting
Next
Type of chilled water reset selected above
Return water
Zone
Outdoor air Disable
[TYPE] type, reset ratio XXX %
Press (+) (-) to change setting
Next
[TYPE] type, start reset setpoint XXX C
Press (+) (-) to change setting
Next
[TYPE] type, max reset setpoint
Press (+) (-) to change setting
Next
Ice machine control [Disable/Enable]
Press (+) (-) to change setting
Panel ice termination setpoint XXX F
Press (+) (-) to change setting
Next