22
F
ault 191
Low Superheat - Circuit 2: CMR - Superheat < 1°C during more than 1333°C x seconds
Fault 194
Low Evaporator Refrigerant Temperature. - Circuit 1: CMR - Refrigerant temperature < setpoint during more than
30°C x seconds
Fault 195
Low Evaporator Refrigerant Temperature. - Circuit 2: CMR - Refrigerant temperature < setpoint during more than
30°C x seconds
Fault 198
Low Oil Flow - Compressor A: CMR - Oil flow switch open during more than 20 seconds
Fault 199
Low Oil Flow - Compressor B: CMR - Oil flow switch open during more than 20 seconds
Fault 19A
low Oil Flow - Compressor C: CMR - Oil flow switch open during more than 20 seconds
Fault 19b
Low Oil Flow - Compressor D: CMR - Oil flow switch open during more than 20 seconds
Fault 19C
Phase Loss - Compressor A: CMR - Loss of 1 or more phases
Fault 19d
Phase Loss - Compressor B: CMR - Loss of 1 or more phases
Fault 19E
Phase Loss - Compressor C: CMR - Loss of 1 or more phases
Fault 19F
Phase Loss - Compressor D: CMR - Loss of 1 or more phases
Fault 1A0
Power Loss - Compressor A: CAR - Loss of all three phases in operation
Fault 1A1
Power Loss - Compressor B: CAR - Loss of all three phases in operation
Fault 1A2
Power Loss - Compressor C: CAR - Loss of all three phases in operation
Fault 1A3
Power Loss - Compressor D: CAR - Loss of all three phases in operation
Fault 1A4
Tracer Communication Loss: IFW - Loss of external information
Fault 1A5
Oil Flow Control - Compressor A: CMR - Problem on oil circuit
Fault 1A6
Oil Flow Control - Compressor B: CMR - Problem on oil circuit
Fault 1A7
Oil Flow Control - Compressor C: CMR - Problem on oil circuit
Fault 1A8
Oil Flow Control - Compressor D: CMR - Problem on oil circuit
Fault 1A9
Electronic expansion valve Electric Drive Circuit
- Refrigerant Circuit 1: CMR 1) Electronic expansion valve wiring
2) Defective UCM
3) Defective Electronic expansion valve
4) Defective Electronic expansion valve relay