100
BAS-SVX40K-EN
8. Hit OK, then Send to Device at the bottom of the MI page. The new point will be sent to SC so it is
available for alarming.
How to Connect Air-Fi® Wireless Sensors Directly to SC+
Tracer SC+ supports sensors connected directly to it since version 5.1. Tracer SC+ supports up to 8
networks with six sensors maximum per network allowing a total number of 48 sensors.
Some applications include:
• Refrigerator/Freezer monitoring sensor
• Monitoring sensor for remote area
• Direct connection to devices that cannot be connected to unit controllers. For example VRF.
Notes:
• This application only configures sensors directly connected to the SC+. Any Air-Fi sensor
connected to a unit controller must be configured using the Tracer® TU service Tool.
• Sensor 1 for each network is default enabled.
• More than 1 sensor per network requires SC+ Configuration.
How to Set-up Air-Fi Network on Tracer Synchrony
1. Address, mount and wire the Air-F® Wireless Communications Interface (WCI) and Air-Fi® Wireless
Communications Sensors (WCSs) according to instructions on the Air-Fi® Wireless Communication
Interface (WCI) Installation Instructions (BAS-SVN038*-EN).
2. Open Synchrony and navigate to the Installation menu on the left hand navigator.
3. Select Air-Fi Networks and Sensors link.
4. Select the Create Network button. A new network will be displayed.
5. Edit the BACnet® Network Number if needed. The BACnet® network numbers is provided by
default but can be edited using the pencil icon. BACnet® network numbers should not be duplicated.
6. Click the check icon when finished.
7. Click the trash can icon to delete a network. All sensors in the network will be deleted when the
network is deleted.
Note: Networks reflected here are all the Air-Fi networks on the SC+ including the WCIs connected to
unit controllers.
Using the Tracer® TU Service Tool with a Wireless Network