94
BAS-SVX40K-EN
default averaging behavior.
8. Hit OK, then OK again, then Send to Device.
9. Create a refrigeration monitoring point for sensor 2 by clicking “Create”.
10. Name the point, then select the reference as Sensor 2 > Space Temperature. This creates the point
reference “wci.sensors.2.spaceTemp” and it will not be part of default averaging behavior.
11. Check the Add to SC Temp box if the refrigerator temperature point is desired to be viewed at the
SC level.
12. On the Alarm Conditions tab set up the conditions and actions as needed.
13. Hit OK, then OK again, then Send to Device.
14. Done.
WCS-SB/R Refrigerator Sensor plus Two Averaged Space Temp Sensors Setup
Instructions
Note: The following setup is not possible with BCI/BCI2. Only in UC210, UC400, UC400-B, UC600,
Symbio™ 210/210e, Symbio™ 400/500, Symbio™ 700/800.
When using a WCS-SB/R sensor with an external 10K Type II sensor probe for refrigerator/freezer
monitoring, some setup will be required using Tracer TU. The WCS-SB/R sensor will be brought in as a
space temperature. If there are also space sensors associated to a UC, the refrigerator/freezer
temperature reading will automatically average with the space temperature sensors if the following
Using the Tracer® TU Service Tool with a Wireless Network