RQC-2017-021 Version-1 1/9/18
2
of 8
Page
Crical:FanAutoisonlyusedwhentherestaurantisclosedandthehoodsareturned OFF
Follow programming instrucons in the Installer Guide
Owner Project Requirements:
Installer: Aercompleteingtheprogrammingofthethermostat,lockthe
thermostatusingapassword.ProvidethepasswordandInstallaon,
OperaonandMaintenanceManualtotheFacilityManager
Trane EFLEX - Human Interface Display
Date & Time
Typical Schedule
Dining Room (Non-Breakfast Restrauant)
Event Start End Heating Cooling Thermostat Status
DR - Drive T Open
12:01am 1:00am 60 78
Occupied (Fan ON)
DR - Closed
1:00am 7:00am 60 78
Unccupied (Fan Auto)
DR - Pre-Open
7:00am 10:30am 68 72
Occupied (Fan ON)
DR - Open
10:31am 10:00pm 68 72
Occupied (Fan ON)
DR - Drive T Open
10:01pm 11:59pm 68 72
Occupied (Fan ON)
Typical Schedule
Kitchen (Non-Breakfast Restrauant)
Event Start End Heating Cooling Thermostat Status
KN - Open
12:01am 2:00am 68 72
Occupied (Fan ON)
KN - Closed
2:01am 7:00am 60 78
Unccupied (Fan Auto)
KN - Open
7:00am 11:59pm 68 72
Occupied (Fan ON)
Trane
2018 BAYSENS924 Thermostat Programming - Quick Reference