36
BCX-SVX002A-EN
Table 14. Electric heat section for size BCVE 24 to 60 dimensions (inches) and weights (lb)
Unit
Size
W H A B C D E F G J K
24 24.58 15.06 14.46 10.99 13.50 9.13 1.12 8.67 3.88 5.12 7.23
36 24.58 15.06 14.46 13.54 13.50 9.13 2.06 9.46 4.31 6.39 7.77
48 28.64 15.3 15.52 15.59 13.56 12.12 1.95 11.92 3.90 7.68 7.83
60 28.64 15.32 15.53 18.49 13.56 12.12 0.79 16.91 3.88 9.23 7.69
Unit
Size
L M N P
Q
R S T U
Min Weight Max Weight
24 3.66 0.56 7.09 0.59 3.68 N/A N/A 0.56 5.77 18.00 27.80
36 3.66 0.56 8.13 0.96 3.13 N/A N/A 0.66 7.08 19.10 28.90
48 3.75 0.75 8.64 1.00 3.39 1.02 2.38 N/A N/A 22.50 32.80
60 3.88 0.76 9.94 1.00 2.74 1.17 2.48 N/A N/A 24.70 35.00
Notes:
1. Electric heater is factory mounted on unit discharge face and wired to unit control box.
2. Electric heat may need field-supplied externally-wrapped insulation if the unit is installed in an unconditioned space or if sweating is an issue.
Coil Connections
Table 15. BCHE hydronic coil connection sizes, OD (inches)
Unit Size 1-Row 2-Row 4-Row 6-Row 8-Row
12 5/8 5/8 3/4 3/4 3/4
18 5/8 5/8 3/4 3/4 1-1/8
24 3/4 7/8 7/8 7/8 7/8
36 3/4 3/4 7/8 1-3/8 1-3/8
54 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8
72 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8
90 1-1/8 1-3/8 1-5/8 1-5/8 1-5/8
120 1-1/8 1-3/8 1-5/8 1-5/8 1-5/8
Table 16. BCVE hydronic coil connection sizes, OD (inches)
Unit Size 1-Row 2-Row 4-Row 6-Row 8-Row
24 7/8 7/8 1-1/8 1-1/8 -
36 7/8 7/8 1-1/8 1-1/8 -
48 7/8 7/8 1-1/8 1-1/8 -
60 7/8 7/8 1-1/8 1-1/8 -
72 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8
90 1-1/8 1-3/8 1-5/8 1-5/8 1-5/8
120 1-1/8 1-3/8 1-5/8 1-5/8 1-5/8
Table 17. BCHE DX coil connection sizes, OD (inches)
Unit Size
3-Row 4-Row 6-Row
Suction
Liquid
Suction
Liquid
Suction
Liquid
12 5/8 5/8 5/8 5/8 5/8 5/8
18 5/8 5/8 5/8 5/8 5/8 5/8
Dimensions and Weights