100
BCX-SVX002A-EN
Table 33. Configuration settings of the motor control board (for reference only) (continued)
Description
on Unit Label
User Interface
Name
Typical User Interface
Value
Description
Protect Funct EEhhpptt FFLLAA
This function protects settings on the
board that affect the safety of the
electric heat system, and limit the
maximum current the motor will draw
under any operating condition.
Do NOT change this setting. This setting locks
out the following parameters from being changed,
for safe operation of the unit.
EE11MM11
EE22MM11
EE11MM22
EE22MM22
MMOODD11
MMOODD22
ssII9911
SSII9922
MM11HHII
MM11LLOO
MM22HHII
MM22LLOO
FFPPRRVV
AA1122MM
AA1122BB
AAIIPPUU
Rmp dft (auto
rst)
rrppddff ooffff
This function shortens the ramps for
faster unit commissioning and auto-
resets to off after approximately
15 minutes of power-on operation.
To aid in commissioning of the unit, for
approximately 10–15 minutes, the ramps will be
shortened to quickly observe proper unit behavior
and response to speeds.
Soft Rev ssoofftt vvxx..xxxx
Displays the software version.
Module should be received with most recent
version.
Fan Speed Response Verification
1. After performing controller specific commissioning,
observe the display on the motor control board with the
power on, to the unit. The motor control board display
should display a looping status indicator as follows:
MMttrr11 00 MMttrr22 00 FFSStt11 OOffff FFsstt22
OOffff EEhhEEnn OOnn
Notes:
The
EEhhEEnn
indicator is unit-specific and may
indicate “Off” at this point; refer to thermistor
function for more information.
A representative fan speed of “1080” rpm are
shown in the example below. Each unit is
factory-configured differently and will have
different settings for different fan speeds.
2. While the unit remains on, exercise the fan controls on
the unit, either directly or indirectly through request for
unit heat/cool. Observe the fan spinning, and then
observe the fan display on the motor control board. It
should display a looping status indicator as follows:
For a size 200, 300, 400, 600, or 800 unit (using typical
unit operating fan speeds):
MMttrr11 11008800 MMttrr22 00 FFSStt11 OOnn FFsstt22
OOffff EEhhEEnn OOnn
For a size 1000 or 1200 unit (using typical unit
operating fan speeds):
MMttrr11 11008800 MMttrr22 11008800 FFSStt11 OOnn FFsstt22
oonn EEhhEEnn OOnn
Note: The EhEn indicator is unit-specific and may indicate
“Off” at this point; refer to thermistor function for
more information.
3. OPTIONAL:
While the fan is running, if practical, change the fan
speeds and observe the display temporarily indicate:
rraammpp
Exercise all fan speeds to ensure positive unit
response and to validate any field wiring.
ECM Overview and Setup

Table of Contents