EasyManua.ls Logo

Trane Foundation GCC180-300 - Economizer Set-Up; Drain Pan Condensate Overflow Switch; (Optional); Low Ambient Operation (Optional)

Trane Foundation GCC180-300
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
RT-SVX51L-EN
Table 12. Enthalpy operation with DCV (CO
2
sensor) - 2 speed fan
DCV
OA Good to
economize?
Y1-I Y2-I FAN SPD Y1-O Y2-O
Occupied Unoccupied
Below set
No
Off Off Low 0-v/Off 0-v/Off VENTMIN L Closed
On Off Low 24-v/On 0-v/Off VENTMIN L Closed
On On
High
24-v/On 24-v/On VENTMIN H Closed
Yes
Off Off Low 0-v/Off 0-v/Off VENTMIN L Closed
On Off Low 0-v/Off 0-v/Off
VENTMIN L to Full-Open Closed to Full-Open
On On
High
24-v/On
0-v/Off
(a)
VENTMIN H to Full-Open Closed to Full-Open
Above set
No
Off Off Low 0-v/Off 0-v/Off VENTMIN L to VENTMAX Closed
On Off Low 24-v/On 0-v/Off VENTMIN L to VENTMAX Closed
On On
High
24-v/On 24-v/On VENTMIN H to VENTMAX Closed
Yes
Off Off Low 0-v/Off 0-v/Off VENTMIN L to VENTMAX Closed
On Off Low 0-v/Off 0-v/Off
VENTMIN L to Full-Open Closed to Full-Open
On On
High
DELAY 24-v/On
(b)
0-v/Off
(a)
VENTMIN H to Full-Open Closed to Full-Open
(a)
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been
satisfied.
(b)
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by
turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Economizer Set-Up
Adjusting the minimum position (MIN POS/VENTMAX on
the SETPOINTS menu) sets the required amount of
ventilation air.
Ambient temperature controls the economizing cycle by
sensing the outside air dry bulb temperature. Table 13, p.
36 lists the five selectable dry bulb values (ENTH CURVE)
on the SETPOINTS menu.
Table 13. Single enthalpy and dual enthalpy boundaries (parameters ES1 through ES5)
Enth. Curve
Temp. dry-Bulb (ºF)
Temp. dewpoint
(ºF)
Enthalpy (btu/lb/
da)
Point P1 Point P2
Temp. ºF
Humid.% RH
Temp. ºF
Humid.% RH
ES1 80.0 60.0 28.0 80.0 36.8 66.3 80.1
ES2 75.0 57.0 26.0 75.0 39.6 63.3 80.0
ES3 70.0 54.0 24.0 70.0 42.3 59.7 81.4
ES4 65.0 51.0 22.0 65.0 44.8 55.7 84.2
ES5 60.0 48.0 20.0 60.0 46.9 51.3 88.5
HL 86.0 66.0 32.4 86.0 38.9 72.4 80.3
Note: For differential enthalpy there is a high limit boundary. The high limit boundary is ES1 when there are no stages of mechanical cooling energized and HL
when a compressor stage is energized.
Note: To disable the economizer to do functional testing,
use a 10 mm wrench to completely unsecure the
shaft coupling. After testing, tighten shaft coupling
securely onto damper shaft using minimum 120 lb-in.
(13.6 Nm) to maximum 180 lb-in. (20.3 Nm) torque.
Drain Pan Condensate Overflow Switch
(Optional)
The Condensate Overflow Switch (COF) is utilized to
prevent water overflow from the drain pan. The float switch
is installed on the corner lip of the drain pan. When the
condensate level reaches the trip point, the COF relay
energizes and opens the 24 Vac control circuit which
disables the unit. Once the 24 Vac control circuit is opened,
a delay timer will prevent unit start-up for three minutes.
Low Ambient Operation (Optional)
During low ambient operation, outside air temperature
below 50°F, the Low Ambient Controller will cycle the
outdoor fan motor "Off" and "On" based on discharge
pressure. The indoor fan motor (IDM) will continue to
operate and the outdoor fan will return to normal operation
once the ambient temperature is above 50°F.
Two-Speed Indoor Fan Control
The JADE controller does not control the supply directly but
uses the following input status to determine the speed of
the supply fan and controls the OA damper to the required
position.
Start Up

Table of Contents

Related product manuals