RT-SVX063E-EN
93
Controls
Constant Volume System
Controls
Constant Volume Zone Panel
(BAYSENS108*)
This electronic sensor features four system switch
settings (Heat, Cool, Auto, and Off) and two fan settings
(On and Auto). It is a manual or automatic changeover
control with dual setpoint capability.
Compressor Motor Winding
Thermostats
CSHD Compressors
The compressors contain an internal line break
overload which stops the compressors under a number
of operating conditions that cause excessive motor
temperature. These include rapid cycling, loss of
charge, abnormally high suction temperatures,
excessive amperage, phase loss and low voltage
CSHN Compressors
PTC sensors are embedded in the motor windings of
each Scroll compressor. These sensors are wired to the
protection module which protects the motor from over
temperature that can occur under a number of
abnormal operating conditions. These include rapid
cycling, loss of charge, abnormally high suction
temperatures, low voltage and excessive amperage.
VZH Variable Speed Compressors
Over current and over torque protection for VZH
compressors are provided by the inverter.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak RA 20 and is the answer not in the manual?

Trane IntelliPak RA 20 Specifications

General IconGeneral
BrandTrane
ModelIntelliPak RA 20
CategoryAir Conditioner
LanguageEnglish

Related product manuals