14 PKG-SVP01B-EN
General
InformationProgramming
Use Table P-GI-3 to reference factory default setpoints and keep track of setpoint adjustments at start-up. Make necessary adjust-
ments using the setpoint key on the HI.
Table P-GI-3. Default Setpoint Setups.
Factory Preset Changed to: Reference Page #
Daytime warmup - initiate 67 F 57
Daytime warmup - terminate 71 F 57
Low ambient compressor lockout (std. units) 50 F 60
Supply air temp - cooling 55 F 57
Supply air temp - heating 100 F 57
Unoccupied zone temp - cool 85 F 58
Unoccupied zone temp - heat 60 F 58
Unoccupied zone temp - MWU 72 F 58
Use Table P-GI-4 to reference function setups and keep track of start-up adjustments. Make necessary adjustments using the setup
key on the HI.
Table P-GI-4. Function (Enable/Disable) Setups.
Factory Preset Changed to: Reference Page #
Compressor lead/lag Disable 34
Daytime warmup Disable 32
Morning warmup Enable 33
Supply air tempering Disable 33
Unoccupied economizer Enable 37
Unoccupied heating Enable 33
Unoccupied mechanical cooling Enable 33