General
InformationProgramming
Use Table P-GI-3 to reference factory default setpoints and keep track of setpoint adjustments at start-up. Make necessary adjust-
ments using the setpoint key on the HI.
Table P-GI-3. Default Setpoint Setups.
Factory Preset Changed to: Reference Page #
Daytime warmup - initiate 67 F 57
Daytime warmup - terminate 71 F 57
Low ambient compressor lockout (std. units) 50 F 60
Supply air temp - cooling 55 F 57
Supply air temp - heating 100 F 57
Unoccupied zone temp - cool 85 F 58
Unoccupied zone temp - heat 60 F 58
Unoccupied zone temp - MWU 72 F 58
Use Table P-GI-4 to reference function setups and keep track of start-up adjustments. Make necessary adjustments using the setup
key on the HI.
Table P-GI-4. Function (Enable/Disable) Setups.
Factory Preset Changed to: Reference Page #
Compressor lead/lag Disable 34
Daytime warmup Disable 32
Morning warmup Enable 33
Supply air tempering Disable 33
Unoccupied economizer Enable 37
Unoccupied heating Enable 33
Unoccupied mechanical cooling Enable 33

Other manuals for Trane IntelliPak Signature Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak Signature Series and is the answer not in the manual?

Trane IntelliPak Signature Series Specifications

General IconGeneral
BrandTrane
ModelIntelliPak Signature Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals