EasyManua.ls Logo

Trane IntelliPak Signature Series - Page 31

Trane IntelliPak Signature Series
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PKG-SVP01B-EN
31
Programming
(On units with GBAS module)
GBAS 0 - 5VDC Module Input 1 0.00 VDC
Assignment: Not Assigned
Possible Values: The inputs 1, 2, 3, and 4 may be assigned to:
Occ Zone Cooling Setpoint
Occ Zone Heating Setpoint
Unocc Zone Cooling Setpoint
Unocc Zone Heating Setpoint
Space Static Pressure Setpoint
Supply Air Static Pressure Setpoint
Min O/A Flow Setpoint
Not Assigned
1. Press the NEXT key to display GBAS 0-5 VDC inputs 2, 3, and 4.
2. Pressing the NEXT key will display the following screen.
(On units with GBAS module)
GBAS (0 - 5VDC) Demand Limit Input Status
OPEN
Possible Values: Open, Closed
1. Pressing the NEXT key will display the following screen.
(On units with GBAS module)
GBAS (0 - 5VDC) Module Relay Output Status
Output 1 OFF
Possible Values: Open, Closed
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
STATUS

Other manuals for Trane IntelliPak Signature Series

Related product manuals