PKG-SVP01B-EN
43
Programming SETUP
(On units with a VCM)
OA Flow CO2 Reset Function: ENABLED
Possible Values: Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with a VCM installed and CO2 reset enabled)
OA Flow CO2 Reset Function: ENABLED
CO2 Start: 800 PPM CO2 Max: 1000 PPM
Possible Values: Enabled, Disabled
CO2 Start = 0-1900 PPM
CO2 Max = 100-2000 PPM
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer with Traq damper)
TRAQ Damper Quantity: 1
TRAQ Damper Size: 28 Inches
Possible Values: Quantity = 1-12
Size = 0, 13, 16, 20, 24, or 28
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
OA Flow Calibration Data:
Gain: 1.0 Offset: 0.0 CCFM
Factory Presets: Gain = 1.0
Offset = 0.0
Possible Values: Gain = 0.0-1.5
Offset = -25.0-25.0
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Ventilation Override Definitions
(On units with a VOM)
Ventilation Override Definitions
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.