RTHD-SVX01K-EN 17
Dimensions and Weights
Unit Dimensions
See unit submittals for specific unit dimensions and water
connection locations.
Unit Weights
Table 5. Weights — standard units (wye-delta starter)
Unit Configuration
(a)
Shipping Weight Operating Weight
lbs kg lbs kg
B1B1B1 9,292 4,215 9,867 4,476
B1C1D1 9,837 4,462 10,554 4,787
B2B2B2 9,402 4,265 10,019 4,545
B2C2D2 9,953 4,515 10,653 4,832
C1D5E4 12,973 5,884 13,673 6,202
C1D6E5 12,780 5,797 13,397 6,077
C1E1F1 14,718 6,676 15,818 7,175
C2D3E3 14,002 6,351 15,044 6,824
C2D4E4 12,972 5,884 13,672 6,201
C2F2F3 16,168 7,334 17,560 7,965
D1D1E1 14,443 6,551 15,385 6,987
D1F1F2 16,187 7,342 17,537 7,955
D1G1G1 18,600 8,437 20,500 9,299
D1G2G2 19,107 8,667 21,065 9,555
D2D2E2 14,562 6,605 15,570 7,062
D2F2F3 16,820 7,629 18,220 8,264
D2G2G1 18,700 8,482 20,700 9,389
D2G3G3 19,508 8,849 21,641 9,816
D3D2E2 14,562 6,605 15,570 7,062
D3F2F3 16,820 7,629 18,220 8,264
D3G2G1 18,650 8,460 20,650 9,367
E3D2E2 14,720 6,677 15,728 7,134
E3F2F3 16,956 7,691 18,356 8,326
E3G2G1 18,800 8,528 20,800 9,435
E3G3G3 19,653 8,915 21,786 9,882
Notes:
1. All weights +/- 3%
2. Shipping weights include standard 150 psig water boxes, refrigerant charge and oil charge.
3. Operating weights include refrigerant, oil and water charges.
(a) Unit configuration digits 1, 2 - compressor code (also shown in unit model number digits 6, 7); digits 3, 4 - evaporator code (unit
model number digits 14, 15); digits 5, 6 - condenser code (unit model number digits 21, 22).