Installation Mechanical
22 RTHD-SVX01K-EN
Lifting Procedure
Figure 7. Rigging configuration
(a)
(a) Optional AFD is not shown. See Figure 3, p. 9 for location of optional AFD. Rigging information is same for wye-delta or AFD units.
Anti-rolling
Cable
F (min)
Evaporator
A
Eyelet or M16
Internal Thread
Lifting
Holes
44.5mm dia typ
Starter
Controls
Anti-rolling
Cable
Condenser
Unit Model Number Location
B
DC
E
Table 7. Rigging dimensions
Unit
Configuration
(a)
Dimension - in (mm)
Units A B C D E F
B1B1B1 in 120 108 56.97 3.92 21.02 24
mm 3048 2743 1447 97 534 610
B1C1D1 in 144 132 58.23 3.74 20.51 24
mm 3658 3353 1479 95 521 610
B2B2B2 in 120 108 58.11 3.86 21.06 24
mm 3048 2743 1476 98 535 610
B2C2D2 in 144 132 58.31 3.66 20.59 24
mm 3658 3353 1481 93 523 610
C1D5E4 in 120 108 59.96 8.62 22.99 24
mm 3048 2743 1523 219 584 610
C1D6E5 in 120 108 60 8.58 22.91 24
mm 3048 2743 1524 218 582 610
C1E1F1 in 144 132 63.50 5.08 24.57 24
mm 3658 3353 1613 129 624 610
C2D3E3 in 120 108 59.72 8.86 24.33 24
mm 3048 2743 1517 225 618 610
C2D4E4 in 120 108 59.96 8.62 22.99 24
mm 3048 2743 1523 219 584 610
C2F2F3 in 144 132 63.4 3.98 24.29 24
mm 3658 3353 1610 101 617 610
D1D1E1 in 120 108 60 7.36 24.09 24
mm 3048 2743 1524 187 612 610
D1F1F2 in 144 132 63.46 3.9 24.49 24
mm 3658 3353 1612 99 622 610
D1G1G1 in 144 132 63.46 3.9 25.75 24