Installation Electrical
48 RTHD-SVX01K-EN
Important:
For factory provided AFD units, verify jumper has
been removed.
For field installed drives, remove jumper shown in
Figure 21.
AFD Drive Programming
Field replacement drives must be programmed via the
keypad interface. Program non-compressor specific
parameters first in sequential order (Table 16), followed by
compressor specific parameters (see Table 17) in
sequential order.
Figure 21. AFD jumper
NOTICE
Equipment Damage!
Changing default clockwise phase rotation or enabling
phase reversal protection could prevent proper chiller
operation or cause equipment damage.
Do NOT change Adaptive Frequency™ drive (AFD)
phase rotation to counterclockwise.
Do NOT enable phase reversal protection.
Jumper between
terminals 12 and 37
must be removed
prior to unit
operation.
Table 16. Non-compressor specific parameter settings
ID Description Setting
0-03 Region Settings North American
0-20 Display Line 1.1 Small DC Link Voltage
0-22 Display Line 1.3 Heatsink Temp.
0-24 Display Line 3 Large Analog Input 53
0-40 [Hand on] Key on LCP Disabled
0-41 [Off] Key on LCP Disabled
0-60 Main Menu Password 999
0-61 Access to Main Menu w/o Password Read Only
1-03 Torque Characteristics Compressor Torque
1-71 Start Delay 0s
1-73 Flying Start Disabled
1-78 Compressor Start Max Speed [Hz] 20Hz
1-79 Compressor Start Max Time to Trip 10s
1-87 Trip Speed Low [Hz] 25Hz
3-02 Min Reference 30Hz
3-41 Ramp 1 Ramp up Time 10s
3-42 Ramp 1 Ramp Down Time 10s
3-82 Starting Ramp Up Time 5s
4-10 Motor Speed Direction Clockwise
4-12 Motor Speed Low Limit [Hz] 30Hz
4-18 Current Limit Max
5-02 Terminal 29 Mode Output
5-12 Terminal 27 Digital Input Coast Inverse
5-31 Terminal 29 Digital Output Alarm
5-40 Function Relay 1 No Operation
6-10 Terminal 53 Low Voltage 2V
6-14 Terminal 53 Low Ref./Feedb. Value 30Hz
6-50 Terminal 42 Output Power 4-20mA
14-00 Switching Pattern SFAVM
14-03 Overmodulation Off
14-10 Mains Failure [4] Kinetic Back-Up
14-12 Function at Mains Imbalance Derate
14-21 Automatic Restart Time 8s
14-50 RFI Filter Off
14-51 DC Link Compensation On
14-60 Function at Over Temperature Derate
14-61 Function at Inverter Overload Derate
14-62 Inv. Overload Derate Current 75%