Dimensions and Weights
RTHD-SVX01K-EN 19
Service Clearances
Notes:
• Required vertical clearance above unit is 36” (914 mm).
There should be no piping or conduit located over the
compressor motor.
• Maximum clearances are given. Some units
configurations may require less clearance than others
in the same category.
• If the room configuration requires a variance to the
clearance dimensions, contact your Trane sales office
representative.
Figure 5. Service clearances
(a)
(a) Optional AFD is not shown. See Figure 3, p. 9 for location of optional AFD.
3’-0” (914mm)
Service Clearance
END VIEW
3’-0” (914 mm)
Service Clearance
3’-0” (914mm)
Service Clearance
(Opposite
Tube Removal)
3’-0”
(914mm)
Service
Clearance
26.4” (671mm)
Radius
36.5” (927mm)
Radius
105° Swing
Tube Removal
Clearance
(Either End)
EDE, DDE, CDE, BBB:
108” (2743mm)
EFF, DFF, CEF, BCD:
126” (3200mm)
EGG, DGG, CGG:
130” (3302mm)
TOP VIEW