Dimensions and Weights
RTHD-SVX01K-EN 19
Service Clearances
Notes:
Required vertical clearance above unit is 36” (914 mm).
There should be no piping or conduit located over the
compressor motor.
Maximum clearances are given. Some units
configurations may require less clearance than others
in the same category.
If the room configuration requires a variance to the
clearance dimensions, contact your Trane sales office
representative.
Figure 5. Service clearances
(a)
(a) Optional AFD is not shown. See Figure 3, p. 9 for location of optional AFD.
3’-0” (914mm)
Service Clearance
END VIEW
3’-0” (914 mm)
Service Clearance
3’-0” (914mm)
Service Clearance
(Opposite
Tube Removal)
3’-0”
(914mm)
Service
Clearance
26.4” (671mm)
Radius
36.5” (927mm)
Radius
105° Swing
Tube Removal
Clearance
(Either End)
EDE, DDE, CDE, BBB:
108” (2743mm)
EFF, DFF, CEF, BCD:
126” (3200mm)
EGG, DGG, CGG:
130” (3302mm)
TOP VIEW