Installation Mechanical
RTHD-SVX01K-EN 23
Important: Rigging dimensions given in Table 7 are
given as a starting point reference. Lifting
cables should be adjusted as necessary for
even unit lift.
Note: If absolutely necessary, the chiller can be pushed or
pulled across a smooth surface if it is bolted to
wood shipping mounts.
1. See Table 5, p. 17 or Table 6, p. 18 for unit shipping
weights.
Note: Weights are typical for units with R-134a
charge.
mm 3658 3353 1612 99 654 610
D1G2G2 in 144 132 63.54 3.82 26.02 24
mm 3658 3353 1614 97 661 610
D2D2E2 in 120 108 59.96 7.4 24.17 24
mm 3048 2743 1523 188 614 610
D2F2F3 in 144 132 63.39 3.98 24.29 24
mm 3658 3353 1610 101 617 610
D2G2G1 in 144 132 63.46 3.9 25.75 24
mm 3658 3353 1612 99 654 610
D2G3G3 in 144 132 63.46 3.9 25.75 24
mm 3658 3353 1612 99 654 610
D3D2E2 in 120 108 60 7.4 24.17 24
mm 3048 2743 1523 188 614 610
D3F2F3 in 144 132 63.39 3.98 24.29 24
mm 3658 3353 1610 101 617 610
D3G2G1 in 144 132 63.46 3.9 25.75 24
mm 3658 3353 1612 99 654 610
E3D2E2 in 120 108 60 4.57 24.09 24
mm 3048 2743 1525 116 612 610
E3F2F3 in 144 132 63.46 1.14 24.21 24
mm 3658 3353 1612 29 615 610
E3G2G1 in 144 132 63.82 0.79 26 24
mm 3658 3353 1621 20 661 610
(a)Designator corresponds to digits 6, 7, 14, 15, 21 and 22 of model number.
Table 7. Rigging dimensions (continued)
Unit
Configuration
(a)
Dimension - in (mm)
Units A B C D E F
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could
result in unit dropping and possibly crushing operator/
technician which could result in death or serious injury,
and equipment or property-only damage. Test lift unit
approximately 24 inches (61 cm) to verify proper center
of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level.
WARNING
Risk of Unit Tipping!
Failure to do so may result in death or serious injury
should a lifting cable fail. Connect an anti-rotation strap
between the lifting beam and compressor before lifting
unit.
WARNING
Shipping Mounts!
Do not use the threaded holes in the compressor to lift
or assist in lifting the unit. They are not intended for
that purpose and could create a dangerous situation.
Do not remove the wood mounts until the unit is in its
final location. Removal of wood shipping mounts prior
to unit final locating could result in death or serious
injury or equipment damage.
NOTICE
Equipment Damage!
Never use a forklift to move the unit. The skid is not
designed to support the unit at any one point and
using a forklift to move the equipment may cause unit
damage. Always position the lifting beam so that
cables do not contact the unit. Failure to do so may
result in unit damage.