Appendix C - Active Alarm List
ARTC-SVX005A-EN 77
cpCOe WRONG CONFIG Alarm Client Auto Reset Warning
UI1 SENSOR FAILURE Client / Server Auto Reset Shuts down local cooling control ***
UI2 SENSOR FAILURE Client / Server Auto Reset Shuts down local cooling control ***
UI3 SENSOR FAILURE Client / Server Auto Reset Shuts down local heating control ***
UI4 SENSOR FAILURE Client / Server Auto Reset Shuts down module if ‘LP Alarm Mode = Sensor’
UI5 SENSOR FAILURE Client / Server Auto Reset Shuts down module
UI6 SENSOR FAILURE Client / Server Auto Reset Shuts down local heating control ****
UI7 SENSOR FAILURE Client / Server Auto Reset Warning
UI8 SENSOR FAILURE Client / Server Auto Reset Locks out module if it is running in heating mode
UI9 SENSOR FAILURE Client / Server Auto Reset Warning
UI10 SENSOR FAILURE Client / Server Auto Reset Warning
UI12 SENSOR FAILURE Client / Server Auto Reset Warning
COMPRESSOR 1 WARNING Client / Server Auto Reset Warning
COMPRESSOR 1 FAILURE Client / Server Auto Reset Shuts down compressor 1
COMPRESSOR 1 FAILURE Client / Server Auto Reset Shuts down compressor 1 *****
COMPRESSOR 1 CORESENSE FAILURE Client / Server Auto Reset Shuts down compressor 1
COMP 1 CORESENSE COMMUNICATION
LOST
Client / Server Auto Reset Shuts down compressor 1
COMPRESSOR 2 WARNING Client / Server Auto Reset Warning
COMPRESSOR 2 FAILURE Client / Server Auto Reset Shuts down compressor 2
COMPRESSOR 2 FAILURE Client / Server Auto Reset Shuts down compressor 2*****
COMPRESSOR 2 CORESENSE FAILURE Client / Server Auto Reset Shuts down compressor 2
Comp 2 CORESENSE COMMUNICATION
LOST
Client / Server Auto Reset Shuts down compressor 2
EVD OFFLINE Client / Server Auto Reset Warning
EVD SYSTEM ALARM Client / Server Auto Reset Warning
EVD DRIVER A ALARM Client / Server Auto Reset Warning
EVD DRIVER B ALARM Client / Server Auto Reset Warning
EVAPORATOR FREEZING ALARM Client / Server Operator Reset Locks out module
SOURCE FREEZING ALARM Client / Server Operator Reset Locks out module
PHASE MONITOR ALARM Client / Server Auto Reset Locks out module
EVAPORATOR FLOW ALARM Client / Server Operator Reset Locks out module
CONDENSOR FLOW ALARM Client / Server Operator Reset Locks out module
SOURCE FLOW ALARM Client / Server Operator Reset Locks out module
CONDENSOR LWT TOO LOW Client / Server Auto Reset Warning
EVAPORATOR LWT TOO HIGH Client / Server Auto Reset Warning
HP ALARM Client / Server Operator Reset Locks out module
HP SWITCH ALARM Client / Server Auto Reset Locks out module
LP ALARM Client / Server Operator Reset Shuts down module
LP Lockout ALARM Client / Server Operator Reset Locks out module
ERROR IN THE NUMBER OF RETAIN
MEMORY WRITINGS
Client / Server Operator Reset Warning
ERROR in RETAIN MEMORY WRITINGS Client / Server Operator Reset Warning
WRONG TEMPERATURE CONTROL
PARAMETERS
Client / Server Auto Reset Warning
WRONG LOCAL ROTATION CONTROL
PARAMETERS
Client / Server Auto Reset Warning
MASTER COMMUNICATION LOST Server Auto Reset Switches slave module to stand-alone mode
INCOMPLETE SAFETY CYCLE Client / Server Auto Reset Warning
cpCOe #2 OFFLINE ALARM Client / Server Auto Reset Switches master and slave modules in stand-alone mode