ACC-SVN231C-EN 13
Minimum Position Setting – FIADMPR101*/102*/103*
To adjust the minimum position setting and check out the
economizer, the power must be connected.
1. Close the unit disconnect and place the zone sensor fan
selector in the fan ON position and the heat/cool selector
in the OFF position. This will place the damper in the
minimum ventilation position.
2. To adjust the minimum position setting for the required
ventilation air, use the Symbio service and installation
mobile app or Symbio™ 700 on-board UI to adjust the
economizer minimum position setpoint BAS in the fresh/
return air settings menu. The damper will open to this
setting each time the blower circuit is energized.
When adjusting minimum position, the damper may
move to the new setting in several small steps. Once the
damper has remained in position for 10 to15 seconds
without movement, it can be assumed it is at the new
position.
3. Replace the filter access panel.
The damper will close when the blower circuit is
de-energized.