Table 15 – General Data for Partial Heat recovery CXAF 080-190 Standard Efficiency
CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF
80 90 100 80 90 100 110 130 140 150 165 180 190
SSE SSE SSE SE SE SE SE SE SE SE SE SE SE
Partial Heat recovery (PHR) option
Heat-Exchanger
Type
Stainless steel Copper Brazed plate Heat exchanger
Digit 19=N or C
Heat-Exchanger
Model
B12MT/
D-60
B12MT/
D-80
B12MT/
D-80
B12MT/
D-60
B12MT/
D-80
B12MT/
D-80
B35TM4/
D-48
B35TM4/
D-48
B35TM4/
D-64
B35TM4/
D-64
B35TM4/
D-64
B35TM4/
D-64
B35TM4/
D-64
Water connection
size (Thread
connection)
(in)
-(mm)
1"1/2 -
48.3
2” -
60.3
2” -
60.3
1"1/2 -
48.3
2” -
60.3
2” -
60.3
2” -
60.3
2” -
60.3
2”1/2 -
76.1
2”1/2 -
76.1
2”1/2 -
76.1
2”1/2 -
76.1
2”1/2 -
76.1
Water content
volume
(l) 1.8 2.4 2.4 1.8 2.4 2.4 4.32 4.32 5.76 5.76 5.76 5.76 5.76
Digit 19=P
Heat-Exchanger
Model
B12MT/
D-48
B12MT/
D-48
B12MT/
D-48
B12MT/
D-48
B12MT/
D-48
B12MT/
D-48
B12MT/
D-48
B12MT/
D-60
B35TM4/
D-64
B35TM4/
D-64
B35TM4/
D-64
B35TM4/
D-64
B35TM4/
D-64
Water connection
size (Thread
connection)
(in) -
(mm)
1"1/2 -
48.3
1”1/2 -
48.3
1”1/2 -
48.3
1"1/2 -
48.3
1”1/2 -
48.3
1”1/2 -
48.3
1”1/2 -
48.3
2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3
2”1/2 -
76.1
2”1/2 -
76.1
Water content
volume
(l) 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.8 4.32 4.32 4.32 4.32 4.32
Antifreeze Heater
Max Power Input
(Standard Digit
19=N or C /
Process Digit 19=P)
(W) 60 / 60 60 / 60 60 / 60 60 / 60 60 / 60 60 / 60 120 / 60 120 / 60
120 /
120
120 /
120
120 /
120
120 /
120
120 /
120
Antifreeze Heater
Max Amps
(Standard Digit
19=N or C /
Process Digit 19=P)
(A)
0.15 /
0.15
0.15 /
0.15
0.15 /
0.15
0.15 /
0.15
0.15 /
0.15
0.15 /
0.15
0.3 /
0.15
0.3 /
0.15
0.3 /
0.3
0.3 /
0.3
0.3 /
0.3
0.3 /
0.3
0.3 /
0.3
Table 16 – General Data for Partial Heat recovery CXAF 080-190 High Efficiency
CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF CXAF
80 90 100 80 90 100 110 130 140 150 165 180 190
SHE SHE SHE HE HE HE HE HE HE HE HE HE HE
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger
Digit 19=N or C
Heat-Exchanger Model
B12MT/
D-60
B12MT/
D-80
B12MT/
D-80
B12MT
/D-60
B12MT
/D-80
B12MT
/D-80
B35TM4
/D-48
B35TM4
/D-48
B35TM4
/D-64
B35TM4
/D-64
B35TM4
/D-64
B35TM4
/D-64
B35TM4
/D-64
Water connection size
(Thread connection)
(in)
-(mm)
1"1/2 -
48.3
2” -
60.3
2” -
60.3
1"1/2 -
48.3
2" -
60.3
2" -
60.3
2" -
60.3
2" -
60.3
2"1/2 -
76.1
2"1/2
-76.1
2"1/2
-76.1
2"1/2
-76.1
2"1/2
-76.1
Water content volume (l) 1.8 2.4 2.4 1.8 2.4 2.4 4.32 4.32 5.76 5.76 5.76 5.76 5.76
Digit 19=P
Heat-Exchanger Model
B12MT/
D-48
B12MT/
D-48
B12MT/
D-48
B12MT/
D-48
B12MT/
D-48
B12MT/
D-48
B12MT/
D-48
B12MT/
D-60
B35TM4/
D-48
B35TM4/
D-48
B35TM4/
D-48
B35TM4/
D-64
B35TM4/
D-64
Water connection size
(Thread connection)
(in)
-(mm)
1"1/2 -
48.3
1”1/2 -
48.3
1”1/2 -
48.3
1"1/2 -
48.3
1”1/2 -
48.3
1”1/2 -
48.3
1”1/2 -
48.3
2” -
60.3
2” - 60.3 2” - 60.3 2” - 60.3
2”1/2 -
76.1
2”1/2 -
76.1
Water content volume (l) 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.8 4.32 4.32 4.32 4.32 4.32
Antifreeze Heater Max
Power Input (Standard
Digit 19=N or C /
Process Digit 19=P)
(W) 60 / 60 60 / 60 60 / 60 60 / 60 60 / 60 60 / 60
120 /
60
120 /
60
120 /
120
120 /
120
120 /
120
120 /
120
120 /
120
Antifreeze Heater Max
Amps (Standard Digit
19=N or C / Process
Digit 19=P)
(A)
0.15 /
0.15
0.15 /
0.15
0.15 /
0.15
0.15 /
0.15
0.15 /
0.15
0.15 /
0.15
0.3 /
0.15
0.3 /
0.15
0.3 / 0.3 0.3 / 0.3 0.3 / 0.3 0.3 / 0.3 0.3 / 0.3