Table 4 – General data CGAF 090-150 Standard Efficiency – Shell & Tube
CGAF CGAF CGAF CGAF CGAF CGAF
90 100 110 130 140 150
SE SE SE SE SE SE
Net Cooling Capacity (1) (kW) 322.4 352.4 390.9 425.0 494.5 522.5
Net Total Power input in cooling (1) (kW) 101.8 116.1 133.6 153.1 163.8 179.0
Unit electrical data (1) (2) (3) (4)
Short Circuit Unit Capacity (kA) 15 15 15 15 15 15
Power Cable Cross Section (max) mm² 1*240 1*240 1*240 1*240 2*300 2*300
Disconnect switch size (A) 400 400 500 500 630 630
Digit 56=1
Maximum Power input (kW) 142.0 161.1 175.3 189.5 220.8 240.0
Unit rated amps (A) 233.4 261.9 289.7 317.5 360.6 389.1
Unit start up amps (w/o soft starter - digit 54=A)
(4)
(A) 466.6 495.1 628.0 655.8 593.8 622.3
Unit start up amps (with soft starter - Digit 54=B)
(4)
(A) 349.0 377.5 462.8 490.6 476.2 504.7
Displacement power factor (dpf) (dpf) 0.88 0.89 0.87 0.86 0.88 0.89
Digit 56=2
Maximum Power input (kW) 142.9 162.0 176.2 190.4 222.0 241.2
Max. amps (A) 231.6 260.1 287.9 315.7 358.2 386.7
Unit start up amps (w/o soft starter - Digit 54=A)
(4)
(A) 464.8 493.3 626.2 654.0 591.4 619.9
Unit start up amps (with soft starter - Digit 54=B)
(4)
(A) 347.2 375.7 461.0 488.8 473.8 502.3
Displacement power factor (dpf) (dpf) 0.89 0.90 0.88 0.87 0.89 0.90
Digit 56=3
Maximum Power input (kW) 144.5 163.6 177.9 192.1 224.2 243.3
Max. amps (A) 234.0 262.5 290.3 318.1 361.4 389.9
Unit start up amps (w/o soft starter - Digit 54=A)
(4)
(A) 467.2 495.7 628.6 656.4 594.6 623.1
Unit start up amps (with soft starter - Digit 54=B)
(4)
(A) 349.6 378.1 463.4 491.2 477.0 505.5
Displacement power factor (dpf) (dpf) 0.89 0.90 0.88 0.87 0.90 0.90
Compressor
Compressor Number per Circuit # 2 2 2 2 3 3
Type Scroll Scroll Scroll Scroll Scroll Scroll
Model Circuit 1 / Circuit 2 kW 25+30/25+30 30+30/30+30 30+40/30+40 40+40/40+40
25+30+30/
25+30+30
30+30+30/
30+30+30
Max Comp Power input Circuit 1 / Circuit 2 kW 28.4+38.2
38.2+38.2/
38.2+38.2
38.2+45.2/
38.2+45.2
45.2+45.2/
45.2+45.2
28.4+38.2+38.2/
28.4+38.2+38.2
38.2+38.2+38.2/
38.2+38.2+38.2
Rated Amps Circuit 1 / Circuit 2 (A)
47+61/
47+61
61+61/
61+61
61+75/
61+75
75+75/
75+75
47+61+61/
47+61+61
61+61+61/
61+61+61
Locked Rotor Amps Circuit 1 / Circuit 2 (direct
start - Digit 54=A)
(A)
260+294/
260+294
294+294/
294+294
294+413/
294+413
413+413/
413+413
260+294+294/
260+294+294
294+294+294/
294+294+294
Locked Rotor Amps Circuit 1 / Circuit 2 (Soft
starter - Digit 54=B)
(A)
156+176/
156+176
176+176/
176+176
176+248/
176+248
248+248/
248+248
156+176+176/
156+176+176
176+176+176/
176+176+176
Motor RPM (rpm) 2900 2900 2900 2900 2900 2900
Oil sump heater Circuit 1 / Circuit 2 (W)
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90+90/
90+90+90
90+90+90/
90+90+90
Evaporator
Quantity # 1 1 1 1 1 1
Type Shell & Tube Heat exchanger
Evaporator model 3511 3511 3511 3511 3519 3519
Evaporator Water Content volume (l) -- -- -- -- -- --
Unit Connections
Without pump package and no strainer
Inlet / Outlet 8" / 8" 8" / 8" 8" / 8" 8" / 8" 8" / 8" 8" / 8"
Without pump package but strainer
Inlet / Outlet 4" / 8" 4" / 8" 4" / 8" 4" / 8" 5" / 8" 5" / 8"
With pump package but no balance valve
Inlet / Outlet 4" / 8" 4" / 8" 4" / 8" 4" / 8" 5" / 8" 5" / 8"
With pump package and balance valve
Inlet / Outlet 4" / 4" 4" / 4" 4" / 4" 4" / 4" 5" / 5" 5" / 5"
Hydraulic Module Components
Single pump - Standard head pressure option
Max available Head Pressure (kPa) 124 109 147 130 122 107
Motor Power (kW) 5.5 5.5 7.5 7.5 7.5
7.5
Rated Amps (A) 11 11 14.4 14.4 14.4 14.4
General Data