CG-SVX039C-GB
21
CGAF CGAF CGAF CGAF CGAF CGAF
90 100 110 130 140 150
SE SE SE SE SE SE
System data
Nb of refrigerant circuit # 2 2 2 2 2 2
Minimum cooling load % (6) % 23 25 21 25 15 17
Total number of capacity steps # 8 4 8 4 14 6
Standard/Partial Heat Recovery Unit
R410A refrigerant charge Circuit 1 / Circuit 2 (kg) 20 / 20 20 / 20 20 / 20 20 / 20 30 / 30 30 / 30
Oil charge Circuit 1 / Circuit 2 (Digit 19 = N/C) (l) 14.5 / 14.5 14.6 / 14.6 14.5 / 14.5 14.4 / 14.4 22.3 / 22.3 22.4 / 22.4
Oil charge Circuit 1 / Circuit 2 (Digit 19 = P) (l) 15.5 / 15.5 15.6 / 15.6 15.5 / 15.5 15.4 / 15.4 23.3 / 23.3 23.4 / 23.4
POE Oil type OIL058E / OIL057E
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances, on a given unit,
consult Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
(6) For detail information refer submittal drawing which are available in the unit.
Table 4 – General data CGAF 090-150 Standard Efficiency – Shell & Tube (continued)