BAS-SVP039C-EN
Profile Definition and Network Variables
The following tables are sorted as follows:
Tables are listed by unit/profile type and sorted by network variable number.
Tables are sorted by name and provide a complete list of names, types, values/ranges, and
descriptions.
NNoottee:: Not all points are available to the user. The available data points are defined during
self-configuration and are dependent on the type of equipment.
Table 1. SCC Network Variable Inputs
NV# Name RecvHrtBt SNVT
Description
37
nviApplicMode
SNVT_hvac_mode
Heat Cool Mode Request
38 nviAuxHeatEnable
SNVT_switch
Heat Auxiliary Enable
39
nviBldgStaticSP SNVT_press_p Building Static Pressure Setpoint
40
nviBldgStatPress
SNVT_press_p Building Static Pressure
41
nviComprEnable
SNVT_switch
Compressor Cooling Enable BAS
42 nviCWFlow
SNVT_switch
Condenser Water Flow BAS
43 nviDAClSP
SNVT_temp_p Discharge Air Cooling Setpoint BAS
44 nviDAHtSP
SNVT_temp_p Discharge Air Heating Setpoint BAS
45 nviDAReheatSP
SNVT_temp_p Discharge Air Reheat Setpoint BAS
46 nviDehumEnable
UNVT_switch_binary Dehumidification System Enable BAS
47 nviEconEnable
UNVT_switch_multistate
Economizer Enable BAS
48
nviEmergOverride SNVT_hvac_emerg Emergency Override BAS
49 nviHumEnable
UNVT_switch_binary
Humidification Enable BAS
50 nviOAMinPos
SNVT_lev_percent
Economizer Minimum Position
Setpoint
51 nviOccManCmd
SNVT_lev_percent Occupancy Request
52 nviOccSchedule
SNVT_lev_percent Occupancy Request
53 nviOccSensor
SNVT_occupancy Occupancy Input BAS
54 nviOutdoorRH
SNVT_lev_percent Outdoor Air Relative Humidity BAS
55
nviOutdoorTemp
SNVT_temp_p Outdoor Air Temperature BAS