Communication Setup and Configuration
The Symbio™ 800 controller can be factory ordered with a specific protocol configuration and
rotary address setting. If communication options were not specified, the Symbio™ 800 controller
will be setup for BACnet TP communications at 76,800 bps with a rotary address setting of 000.
Figure 1. Symbio™™ 800 rotary address and service tool port
Service Tool for Symbio™™ 800 Configuration
The service tool used to modify the Symbio™ 800 controller is a standard web browser. The
Symbio™ 800 webpage is accessed by using a standard USB type A/B cable. Connect the USB
cable between a laptop and the service tool port on the Symbio™ 800 controller (shown in Figure
1, p. 6).
Connecting to the Symbio™™ 800 Web Interface
1. Connect a laptop to the Symbio™ 800 controller using a USB cable.
2. On the laptop, open a web browser to http://198.80.18.1/
3. When the Symbio™ 800 page displays, click LLoogg IInn.