Trane Symbio 800 - Page 22

Trane Symbio 800
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
BAS-SVP039C-EN
Table 5. DAC Network Variable Outputs (continued)
NV# Name Send HrtBt SNVT
Description
129
nvoStartsRunTmF
UNVT_starts_runtime
Starts - Compressor 2C
SNVT_count_f
Starts
SNVT_time_f
Run Time
130 nvoStatus
SNVT_obj_status Local Setpoint Control
131
nvoSucRfgtPrsC1
SNVT_press_f
Suction Refrigerant Pressure, Circuit
1
132
nvoSucRfgtPrsC2
SNVT_press_f
Suction Refrigerant Pressure, Circuit
2
133
nvoSucRfgtTmpC1
SNVT_temp_p
Suction Refrigerant Temperature,
Circuit 1
134
nvoSucRfgtTmpC2
SNVT_temp_p
Suction Refrigerant Temperature,
Circuit 2
135
nvoDschRfgtPrsC1
SNVT_press_f
Discharge Refrigerant Pressure,
Circuit 1
136
nvoDschRfgtPrsC2
SNVT_press_f
Discharge Refrigerant Pressure,
Circuit 2
137
nvoDisSatRfgTmp1
SNVT_temp_p
Discharge Refrigerant Temperature,
Circuit 1
138
nvoDisSatRfgTmp2
SNVT_temp_p
Discharge Refrigerant Temperature,
Circuit 2
139 nvoAirFlowPctC1
SNVT_lev_percent Air Flow Percentage, Circuit 1
140 nvoAirFlowPctC2
SNVT_lev_percent Air Flow Percentage, Circuit 2
141
nvoSupFanOnOff
SNVT_switch
Supply Fan Output Status
142
nvoSupFanStatus
SNVT_switch
Supply Fan Speed Status
143 nvoTraneVar9
UNVT_c5s
Manufacturer-defined
144
nvoUnitCurrent
UNVT_3phase_current
Unit Current Per Line
nvoUnitCurrent (bytes 1-
2)
SNVT_amp_ac Current L1, in Amps
nvoUnitCurrent (bytes 3-
4)
SNVT_amp_ac Current L2, in Amps
nvoUnitCurrent (bytes 5-
6)
SNVT_amp_ac Current L3, in Amps
nvoUnitCurrent (bytes 7-
8)
Invalid
nvoUnitCurrent (bytes 9-
10)
Invalid
nvoUnitCurrent (bytes 11-
12)
Invalid
145 nvoUnitPower
SNVT_power_f Unit Power Consumption
146
nvoUnitStatus
SNVT_hvac_status
Unit Status
nvoUnitStatus (byte 1)
.mode Mode Status
nvoUnitStatus (bytes 2-3)
.heat_output_primary Heating Capacity Primary Status
nvoUnitStatus (bytes 4-5)
.heat_output_secondary Heating Capacity Secondary Status
nvoUnitStatus (bytes 6-7)
.cool_output Cooling Capacity Status
nvoUnitStatus (bytes 8-9)
.econ_output
Economizer Status
nvoUnitStatus (bytes 10-
11)
.fan_output Supply Fan Speed Status
nvoUnitStatus (byte 12)
.in_alarm
In Alarm
147
nvoUnitVoltage
UNVT_3Phase_volt
Unit Voltage
nvoUnitVoltage (bytes 1-2)
SNVT_volt_ac
Voltage AB
nvoUnitVoltage (bytes 3-4)
SNVT_volt_ac
Voltage BC
nvoUnitVoltage (bytes 5-6)
SNVT_volt_ac
Voltage CA
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess