Note: Use 12ga wire.
1. At quad relay output LLID 1A5 in the unit control panel,
disconnect wire 42A from terminal
7.
2. Connect wire 42A to RLY02909 terminal 2.
3. Install a wire between LLID 1A5 terminal 7 and
RLY029
09 term
inal 3.
4. Install a wire from RLY029
09 te
rminal 4 and a common
terminal (1X1-17 is typical).
5. Install a wire from a 120v source terminal (1X1-10 is
typical) that is downstrea
m of breaker 1Q4, to
RLY02909 terminal 1.
Figure 13. Installed solid state relay
Figure 14. Completed schematic