EasyManua.ls Logo

Trane TCAA Series - Page 59

Trane TCAA Series
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ARTC-SVX013A-EN
59
Table 18. Condenser pump controls
Screen User Interface Function Access
Condenser
Pumps Control
Screen has the same features / capabilities as
Evaporator Pumps Control screen (see above).
To access other settings click Setup.
Main Menu
> Devices
Menu >
Pump
button >
Cond Pump
button
Condenser
Pumps Setup
Has the same set of settings as for the
evaporator pumps (see above), except for Run
mode.
Run mode.
SystemPumps start/stop along with the
chiller enable/disable signal;
CompPumps run as long as compressors
are operational.
Main Menu
> Devices
Menu >
Pump
button >
Cond Pump
button >
Setup
button
Primary/Secondary Control (Chiller Array)
The primary/secondary functionality allows an array on n or
n+m chillers to be controlled by one (Primary) controller.
Where n is the number of chillers in the array and m is the
number of chillers in the array that are designated as
Backup nodes.
To enable use primary/secondary functionality, click M/S
Enable button on the HMI Configuration screen to display
Enabled.
It also exposes the Master Slave Config screen via M/S
button.
Figure 33. M/S Enable/Disable button
Table 19. Primary/Secondary chiller management
Screen User Interface Function Access
M/S Enable/
Disable
The left side of this screen provides the
parameters for Primary/Secondary units.
The right side of this screen provides status
information, that details which nodes are
requested to run by the Primary and their
actual running capacity.
Main Menu >
Devices Menu >
M/S
Operating Procedures

Table of Contents

Related product manuals