EasyManua.ls Logo

Trane TCONT824 - System Mode

Trane TCONT824
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation Guide
34 18-HD72D1-6
System Mode
The 824 has (5) System Modes which can be selected…
Heating, Cooling, Off, Emergency Heat and Auto.
• Heating – System will only operate in heating mode
• Cooling – System will only operate in the cooling
mode
• Off – System will not operate in heating or cooling
mode
• Emergency Heating – System will operate the indoor
heat source only (this is only available when the
outdoor unit type is a heat pump)
• Auto - The Control will determine which mode of
operation based on the following rules:
• Heating - Indoor temperature is equal or less than
heating setpoint
• Cooling – Indoor temperature is equal to or greater
than cooling setpoint or within 1°F of cooling setpoint
There is minimum deadband between heating and cooling
setpoints of 3°F
6.8 Fan Mode
The 824 has three Fan Modes:
• Auto – Fan only runs with a call for heating or cooling
• On – Fan runs continuous
• Circ – Fan runs a user selected minimum amount of
time each hour
6.9 Air Cleaner Mode
The 824 has three Air Cleaner modes:
• Auto – Air cleaner operates only with a call for fan
operation
• Quick – Air cleaner will operate for 3-hours
• Allergy – Air cleaner will operate for 24-hours