48 ARTC-SVX002A-EN
Chiller Performance Data
This manual uses a typical 120-ton water-cooled chiller
consisting of four modules with brazed plate evaporators
for example purposes. The model number and a chiller’s
precise configuration can be found on the chiller model
nameplate. See “Model Number and Coding,” p. 7.
Table 9. Typical Manhattan™ water-cooled chiller specification for example purposes
Chiller System (four 30-ton water-cooled chiller modules) Model # TPWCCMV0300D3-MM
Evaporator Type brazed plate Condenser Type brazed plate
Evaporator Flow 300 gpm Condenser flow 260 gpm
Evaporator Fluid 70/30 water/glycol Condenser fluid water
Entering Fluid Temperature 54 °F (12 °C) Entering Fluid Temperature 85 °F (29 °C)
Leaving Fluid Temperature 44 °F (7 °C) Leaving Fluid Temperature 95 °F (37.3 °C)
Evaporator Pressure Drop 4.4 psi Condenser Pressure Drop 3.1 psi
Maximum Operating Pressure 650 psi (refrigerant side) System Capacity 1,503,500 btu/hr. (120 tons)
Refrigerant R410A Connections 6 in. roll grooved
Chiller Modules (4)
Compressors two per module Rated Load Amps 48.4 amps each
Horsepower 15 Total Full Load Amps 96.8 amps per module
Locked Rotor Amps 340 amps Electrical Power Supply 208/60/3
System
Total Full Load Amps 387 amps Maximum Overcurrent Capacity 500 amps
Minimum Circuit Ampacity 394 amps
Dimensions
Each Chiller Module 24 W x 66 L x 77 H in.
(a)
Overall Chiller System 96 W x 66 L x 77 H in.
(b)
Weight
Each Chiller Module 1,600 lbs. Overall Chiller System 6,400 lbs.
(a) Client module is 32 in. wide, including power distribution panel.
(b)Including power distribution panel.