Appendix
102 CNT-SVX05B-EN
Auto Emergency heat Determined by controller Fan enabled
Heating enabled
Cooling disabled
Damper enabled
Auto Fan only Fan only Fan enabled
Heating disabled
Cooling disabled
Damper disabled
Auto Not present Determined by controller Fan enabled
Heating enabled
Cooling enabled
Damper enabled
Heat Any state Heat Fan enabled
Heating enabled
1
Cooling disabled
Damper ventilation enabled
Economizer disabled
Morning warm-up Any state Morning warm-up Fan enabled
Heating enabled
Cooling disabled
Damper closed
Cool Any state Cool or dehumidifying Fan enabled
Heating disabled
1
Cooling enabled
Damper enabled
Night purge Any state Night purge Fan enabled
Heating disabled
Cooling disabled
Damper ventilation disabled
Economizer enabled
Pre-cool Any state Pre-cool Fan enabled
Heating disabled
Cooling enabled
Damper ventilation disabled
Economizer enabled
Table 71. Space temperature control operation based on effective heat/cool output (continued)
Application mode input
(nviApplicMode)
Heat/cool mode input
(nviHeatCool)
Effective heat cool mode
output
(nvoHeatCool)
Unit operation