EasyManuals Logo

Trane Tracer AH540 User Manual

Trane Tracer AH540
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Communication with other controllers
CNT-SVX05B-EN 3
Communication with other controllers
Tracer AH540/541 controllers operates either in stand-alone mode or as
part of a building automation system. In either mode of operation, multi-
ple controllers can be bound (bindings are configured using the Rover ser-
vice tool) to other LonTalk
®
-based controllers so they can communicate
data to one another. Controllers that are bound as peers can share the fol-
lowing data:
Setpoint
Zone temperature
Zone relative humidity
Outdoor air temperature
Occupancy mode
Heating/cooling mode
Fan status
Unit capacity control
Applications having more than one unit serving a single space can benefit
by using this feature; it allows multiple units to share a single space tem-
perature sensor and prevents multiple units from simultaneously heating
and cooling. For more information, see “AH540/541 network variables” on
page 109.