Specifications
CNT-SVX05B-EN 7
Specifications
Dimensions
Controller board
• Height: 5½ in. × 8 in. × 2 in.
• (140 mm × 203 mm × 51 mm)
Termination boards
• Tracer AH540: 3½ in. × 8 in. × 1 in. (89 mm × 203 × 51 mm)
• Tracer AH541, frame-mounted: 10¼ in. × 8 in. × 3½ in.
(260 mm
× 203 mm × 89 mm)
• Tracer AH541 NEMA-1 enclosure: 16½ in. × 14¾ in. × 5½ in.
(418 mm
× 373 mm × 140 m)
Operating environment
•
-40° to 70°C (-40° to 158°F)
• 5% to 95% relative humidity non-condensing
Storage environment
•
-40° to 85°C (-40° to 185°F)
• 5% to 95% relative humidity non-condensing
Agency conformance
UL
• UL unlisted component
• UL 873 Temperature Indicating and Regulating Equipment
• CUL C22.2 No. 24-93 Temperature Indicating and Regulating
Equipment
CE
• Conducted Emissions EN 55022 Class A
EN 55022 Class B
EN 61000-3-2
EN 61000-3-3
• Radiated Emissions EN 55022 Class B
• Immunity EN 50082-2 Industrial
FCC
• CFR 47, Part 15, Subpart A, Class A
• CFR 47, Part 15, Subpart A, Class B
Power requirements
(see Figure 8 on page 16)
• Low-voltage, class 2, non-safety device
• 18 to 32 V ac (24 Vac nominal)
• Maximum VA = 21 VA (control board)
• 50 or 60 Hz