Chapter 4 Sequence of operation
46 CNT-SVX05B-EN
Standby — — — — zero Standby
not zero Bypass
Null Occupied — Occupied — — Occupied
Unoccupied — zero Standby
not zero Bypass
Null Occupied — Occupied
Unoccupied zero Standby
not zero Bypass
Not present — Occupied
Unoccupied — — — zero Unoccupied
not zero Bypass
Standby — — — zero Standby
not zero Bypass
Null Occupied Occupied — — Occupied
Unoccupied — zero Standby
not zero Bypass
Null Occupied — Occupied
Unoccupied zero Standby
not zero Bypass
Not present — Occupied
Unoccupied — — zero Unoccupied
not zero Bypass
Null Occupied — — Occupied
Unoccupied — zero Unoccupied
not zero Bypass
Null Occupied — Occupied
Unoccupied zero Unoccupied
not zero Bypass
Not present — Occupied
Ta b l e 1 8 : Effective occupancy arbitration for Tracer AH540/541 with operator display (continued)
Manual
override
1
(nviOccMan
Cmd)
Commun-
icated
schedule
(nviOcc
Schedule)
Local
schedule
Occupancy
sensor
(nviOcc
Sensor
3
)
Local
occupancy
binary input
Bypass
timer
4
Result
(nvoEffect
Occup)
1 This value is the last enumeration received. It can come from either the nviOccManCmd network variable or the operator dis-
play schedule override.
2 Null = any other value.
3 The variable nviOccSensor is used with the SCC profile only. Refer to the Null rows in this column for the DAC profile.
4 This value represents whether or not the bypass timer is at zero or not. When a bypass request is made, the timer is set to the
value specified in the Occupied Bypass Timer field, and it begins to count down. While it is counting down, the value is not
zero. When the count down is complete, the value is zero.