EasyManuals Logo

Trane Tracer MP501 User Manual

Trane Tracer MP501
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
36 CNT-SVX08F-EN
PID Control
20. Record the measured value when it stabilizes. The temperature stabilizes at 70°F (21°C).
21. Manually control the analog output to 50% or 100%. Control the output to 100% (completely
opening the heating valve).
22. Record the measured value when it stabilizes. The temperature stabilizes at 120°F (49°C)
23. Subtract the measured value determined in step 2 fro
m the measured value determined in step
4. This is the change in the measured value.
120 - 70 = 50°F (49 - 21 = 28°C).
24. Calculate two-thirds (66%) of the change in measured value determined in step 4. Add this value
to
the in
itial temperature to determine at what point two-thirds of the total change occurs.
In the example, 0.66 × 50°F = 33°F, so two thirds of the tota
l change
occurs at 70°F + 33°F = 103°F
(0.66 × 28°C = 18°C; 21 + 18 = 39°C).
25. Again, set the analog output to 0% and allow the measured value to stabilize. The measured
value stabilize
s at 70°F (21°C).
26. Control the output to the value used in step 3 and record the time
it takes to reach the two-thirds
point determined in step 6. This is the system time constant. The time it takes to reach 103°F
(39°C) is 2.5 minutes (150 seconds).
27. Divide the system time constant by 10 to determine
the starting samp
ling frequency.
150 seconds ÷ 10 = 15 seconds.
Note: Th
e system time constant is the time it takes
to reach 63.21% of the difference between the
start point and the end point. Determining two-thirds (66%) is accurate enough for our
purposes.
Figure 18 illustrates the procedure described above.
Figure 18. Determining the system time constant
System time
constant
Time (minutes)
Space temperature (°F)
Initial value (valve closed)
Final value (valve open)
2/3 of total change
Example
This scenario describes finding the sampling frequency for a PID loop controlling a heating
application.
28. Fully close the output.
29. The stabilized temperature reads 60°F (16°C).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer MP501 and is the answer not in the manual?

Trane Tracer MP501 Specifications

General IconGeneral
BrandTrane
ModelTracer MP501
CategoryController
LanguageEnglish

Related product manuals