Table 28. Effective occupancy output
nviOccManCmd nviOccSchedule
Occupancy Sensor
Arbitration Result Bypass Timer nvoEffectOccup
Occupied Does not matter Does not matter Does not matter Occupied
Unoccupied Does not matter
Does not matter
Zero Unoccupied
Not zero Bypass
(a)
(a) Occupied bypass is initiated by either a communicated request (nviOccManCmd = bypass) or a local input (zone sensor timed override ON button).
Bypass
2
Occupied Does not matter Does not matter
(b)
(b)Whenever an update of nviOccManCmd is received indicating Bypass, the bypass timer is set to the nviBypassTime and the countdown starts.
Occupied
Unoccupied Does not matter
Zero
(b)
Unoccupied
Not zero
(b)
Bypass
(a)
Standby Does not matter
Zero
(b)
Standby
Not zero
(b)
Bypass
(a)
Not valid
Occupied Does not matter
(b)
Occupied
Unoccupied
Zero
(b)
Unoccupied
Not zero
(b)
Bypass
(a)
Standby Does not matter Does not matter
Zero Standby
Not zero Bypass
(a)
Not valid
Occupied
Occupied Does not matter Occupied
Unoccupied
Zero Standby
(c)
(c) If nviOccManCmd and nviOccSensor are not valid, nviOccSchedule is occupied, the bypass timer is zero, and the binary input is occupancy. Then, the
occupancy binary input can switch the control between occupied and occupied standby.
Not zero Bypass
(a)
Unoccupied Does not matter
Zero Unoccupied
Not zero Bypass
(a)
Standby Does not matter
Zero Standby
Not zero Bypass
(a)
Not valid
Occupied Does not matter Occupied
Unoccupied
Zero Unoccupied
Not zero Bypass
(a)
CNT-SVX08F-EN 55
Troubleshooting