BAS-SVX48H-EN
55
Table 11. Diagnostics (continued)
Diagnostic
Probable Cause
Consequences Diagnostic Type
Entering Water Temp Failure Invalid or missing value for zone temperature.
Fan Unaffected
(Enabled)
Valves
Unaffected
Outdoor Air
Damper
Unaffected
DX/Electric Heat
Unaffected
Automatic
Discharge Air Temp Low Limit Discharge air temperature has fallen below the Discharge Air
Temperature Low Limit.
Fan OFF
Valves Open
Outdoor Air
Damper Closed
DX/Electric Heat
OFF
Smart reset/manual
Discharge Air Temp Failure Invalid or missing value for discharge air temperature.
Simplified Zone
Control Algorithm
Runs
Unit Shuts OFF if
Zone
Temperature
Fails
Automatic
Outdoor Air Temp failure Invalid or missing value for outdoor air temperature.
Fan Unaffected
Valved
Unaffected
Outdoor Air
Damper
Minimum Position
DX Cooling/
Electric Heat
Unaffected
Automatic
Humidity Input Failure Invalid or missing value for relative humidity.
Fan Unaffected
Valves
Unaffected
Outdoor Air
Damper
Unaffected
DX Cooling/
Electric Heat
Unaffected
Automatic
CO
2
Sensor Failure Invalid or missing value for CO
2
.
Fan Unaffected
Valves
Unaffected
Outdoor Air
Damper
Unaffected
DX Cooling/
Electric Heat
Unaffected
Informational