Table 11. Diagnostics (continued)
Diagnostic
Probable Cause
Consequences Diagnostic Type
Generic AIP Failure Invalid or missing value for generic analog input.
Fan Unaffected
Valves
Unaffected
Outdoor Air
Damper
Unaffected
DX Cooling/
Electric Heat
Unaffected
Informational
Local Fan Mode Failure Invalid or missing fan-speed switch (reverts to default fan
speed).
Fan Unaffected
Valves
Unaffected
Outdoor Air
Damper
Unaffected
DX Cooling/
Electric Heat
Unaffected
Automatic
Local Setpoint Failure Invalid or missing value for zone temperature setpoint
(reverts to default setpoint).
Fan Unaffected
Valves
Unaffected
Outdoor Air
Damper
Unaffected
DX Cooling/
Electric Heat
Unaffected
Automatic
OOuuttppuutt TTeessttiinngg