Table 11. Diagnostics (continued)
Diagnostic
Probable Cause
Consequences Diagnostic Type
Generic AIP Failure Invalid or missing value for generic analog input.
• Fan Unaffected
• Valves
Unaffected
• Outdoor Air
Damper
Unaffected
• DX Cooling/
Electric Heat
Unaffected
Informational
Local Fan Mode Failure Invalid or missing fan-speed switch (reverts to default fan
speed).
• Fan Unaffected
• Valves
Unaffected
• Outdoor Air
Damper
Unaffected
• DX Cooling/
Electric Heat
Unaffected
Automatic
Local Setpoint Failure Invalid or missing value for zone temperature setpoint
(reverts to default setpoint).
• Fan Unaffected
• Valves
Unaffected
• Outdoor Air
Damper
Unaffected
• DX Cooling/
Electric Heat
Unaffected
Automatic