22 CNT-SVX11A-EN
Configuration
Table 11: Bypass timer range
Default Valid Range
Occupancy bypass timer
1
120 minutes 30 to 240 minutes
( 1-minute resolution)
1. The occupied bypass timer is used for timed override applications.
Occupied Bypass Timer
Table 12: Control wait timer
Default Valid Range
Power up control wait (2 minutes) 120 seconds Disable or enable
Power-up Control Wait
Table 13: Maintenance timer range
1
Default Valid Range
Maintenance timer 0 0 to 10,000 hours
Maintenance Timers
1. Based on fan run hours.