22 TWE5-PRC001-EN-10-15-99
Performance
Data Heating English Units
TWA040CD WITH TWE050CA5-C AT 1500 CFM
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F. 60 70 75 80 60 70 75 80
-18 9.68 9.46 9.36 9.25 1.94 2.04 2.08 2.13
-13 11.3 11.1 11.0 10.8 2.02 2.13 2.18 2.23
-8 13.0 12.7 12.6 12.4 2.10 2.21 2.27 2.32
-3 14.6 14.3 14.2 14.0 2.19 2.30 2.36 2.42
2 16.3 15.9 15.8 15.6 2.27 2.39 2.45 2.51
7 17.9 17.6 17.4 17.2 2.35 2.48 2.54 2.61
12 19.6 19.2 19.0 18.8 2.43 2.57 2.63 2.70
17 21.2 20.8 20.6 20.4 2.51 2.65 2.73 2.80
22 22.6 22.1 21.8 21.6 2.59 2.74 2.82 2.89
27 23.9 23.4 23.1 22.8 2.67 2.83 2.91 2.99
32 25.2 24.6 24.4 24.1 2.76 2.92 3.00 3.08
37 26.5 25.9 25.6 25.3 2.84 3.01 3.09 3.17
42 27.8 27.2 26.9 26.6 2.92 3.09 3.18 3.27
47 37.2 36.4 36.0 35.6 3.13 3.32 3.41 3.51
52 39.9 39.0 38.6 38.1 3.23 3.43 3.53 3.63
57 42.5 41.6 41.1 40.7 3.34 3.54 3.64 3.75
62 45.2 44.2 43.7 43.2 3.44 3.65 3.76 3.86
67 47.9 46.8 46.3 45.7 3.54 3.76 3.87 3.98
72 50.5 49.4 48.8 48.3 3.65 3.88 3.99 4.10
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 1500 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW 1325 1700
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1500 CFM
HEATING CAP. (HIGH TEMP.) = 36400 BTUH
HEATING CAP. (LOW TEMP.) = 20800 BTUH
COMPR. POWER (HIGH TEMP.) = 2566 WATTS
COMPR. POWER (LOW TEMP.) = 1900 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF. (LOW TEMP.) = 2.30
OUTDOOR FAN POWER = 244 WATTS
INDOOR FAN POWER = 510 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE
TWA050CD WITH TWE050CA5-C AT 1800 CFM
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F. 60 70 75 80 60 70 75 80
-18 12.5 12.2 12.1 12.0 2.50 2.62 2.67 2.73
-13 14.9 14.6 14.4 14.2 2.60 2.72 2.78 2.84
-8 17.3 16.9 16.7 16.5 2.69 2.82 2.88 2.94
-3 19.7 19.2 19.0 18.8 2.78 2.92 2.98 3.05
2 22.0 21.6 21.3 21.1 2.87 3.02 3.09 3.16
7 24.4 23.9 23.7 23.4 2.97 3.12 3.19 3.27
12 26.8 26.3 26.0 25.7 3.06 3.22 3.30 3.38
17 29.2 28.6 28.3 28.0 3.15 3.32 3.40 3.48
22 30.2 29.5 29.2 28.9 3.25 3.42 3.51 3.59
27 31.1 30.5 30.2 29.8 3.34 3.52 3.61 3.70
32 32.1 31.4 31.1 30.8 3.44 3.63 3.72 3.81
37 33.1 32.4 32.0 31.7 3.54 3.73 3.83 3.92
42 34.0 33.3 33.0 32.6 3.63 3.83 3.93 4.03
47 48.0 47.0 46.5 46.0 4.00 4.23 4.34 4.45
52 51.2 50.1 49.5 49.0 4.14 4.38 4.50 4.61
57 54.3 53.1 52.5 52.0 4.28 4.53 4.65 4.78
62 57.5 56.2 55.6 54.9 4.43 4.68 4.81 4.94
67 60.6 59.3 58.6 57.9 4.57 4.83 4.97 5.10
72 63.7 62.3 61.6 60.9 4.71 4.98 5.12 5.26
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 1800 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW 1575 2025
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1800 CFM
HEATING CAP. (HIGH TEMP.) = 47000 BTUH
HEATING CAP. (LOW TEMP.) = 28600 BTUH
COMPR. POWER (HIGH TEMP.) = 3222 WATTS
COMPR. POWER (LOW TEMP.) = 2313 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.24
COEFF. OF PERF. (LOW TEMP.) = 2.50
OUTDOOR FAN POWER = 255 WATTS
INDOOR FAN POWER = 750 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE
TWA060CD WITH TWE050CA5-C AT 1800 CFM
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F. 60 70 75 80 60 70 75 80
-18 14.0 13.8 13.7 13.5 3.24 3.37 3.43 3.50
-13 16.9 16.6 16.4 16.3 3.36 3.50 3.57 3.64
-8 19.7 19.4 19.2 19.1 3.49 3.64 3.71 3.79
-3 22.6 22.2 22.0 21.8 3.62 3.77 3.85 3.93
2 25.4 25.0 24.8 24.6 3.74 3.91 3.99 4.07
7 28.3 27.8 27.6 27.3 3.87 4.04 4.13 4.22
12 31.1 30.6 30.3 30.1 3.99 4.18 4.27 4.36
17 34.0 33.4 33.1 32.8 4.12 4.31 4.41 4.50
22 35.7 35.1 34.8 34.5 4.52 4.74 4.85 4.95
27 37.4 36.8 36.5 36.2 4.93 5.17 5.28 5.40
32 39.1 38.5 38.2 37.8 5.33 5.59 5.72 5.85
37 40.9 40.2 39.8 39.5 5.74 6.02 6.16 6.30
42 42.6 41.9 41.5 41.2 6.14 6.45 6.60 6.76
47 53.9 53.0 52.5 52.1 5.33 5.59 5.72 5.85
52 57.2 56.3 55.8 55.3 5.53 5.80 5.94 6.08
57 60.6 59.5 59.0 58.5 5.73 6.02 6.16 6.30
62 63.9 62.8 62.3 61.7 5.94 6.23 6.38 6.53
67 67.2 66.1 65.5 64.9 6.14 6.44 6.60 6.75
72 70.5 69.3 68.7 68.1 6.34 6.66 6.82 6.98
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 1800 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW 1575 2025
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1800 CFM
HEATING CAP. (HIGH TEMP.) = 53000 BTUH
HEATING CAP. (LOW TEMP.) = 33400 BTUH
COMPR. POWER (HIGH TEMP.) = 4446 WATTS
COMPR. POWER (LOW TEMP.) = 3166 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.76
COEFF. OF PERF. (LOW TEMP.) = 2.26
OUTDOOR FAN POWER = 395 WATTS
INDOOR FAN POWER = 750 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE