50 RT-PRC024-EN
Performance Data
(12½ Tons High Efficiency)
Table 32. Evaporator Fan Performance 12½ Tons TCD151C Standard or TXV Refrigeration System
Downflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive
(i)
(i)
Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary.
3-HP Standard Motor & Drive
2500* 402 0.30 460 0.39 510 0.48 555 0.56 595 0.64 633 0.74 667 0.83 699 0.92 731 1.02
3250* 378 0.35 447 0.49 503 0.62 552 0.74 595 0.86 634 0.97 672 1.08 706 1.19 739 1.30 769 1.40
4000* 430 0.56 495 0.74 549 0.91 596 1.07 638 1.22 677 1.37 712 1.52 747 1.66 778 1.80 809 1.94
4500 466 0.74 528 0.95 580 1.14 627 1.33 668 1.51 706 1.68 742 1.85 776 2.02 806 2.18 836 2.34
5000 503 0.96 562 1.20 612 1.42 657 1.63 699 1.84 736 2.04 771 2.23 803 2.41 835 2.61 865 2.80
5500 540 1.22 597 1.49 645 1.74 689 1.98 729 2.20 767 2.44 801 2.66 833 2.87 864 3.07 893 3.28
6000 579 1.53 633 1.82 680 2.10 722 2.37 761 2.63 797 2.87 832 3.13 864 3.38 894 3.61 922 3.83
3-HP Standard Motor & High Static Drive Accessory 5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive 3-HP Standard Motor & High Static Drive Accessory
2500* 760 1.11 789 1.21 817 1.31 842 1.41 868 1.51 892 1.60 916 1.71 939 1.81 962 1.91 984 2.01
3250* 798 1.52 827 1.64 853 1.76 880 1.88 905 2.01 928 2.13 953 2.26 976 2.38 998 2.51 1020 2.63
4000* 839 2.07 867 2.21 893 2.33 919 2.47 943 2.59 967 2.73 991 2.88 1013 3.03 1036 3.18 1056.4 3.33
4500 865 2.50 892 2.66 919 2.81 945 2.96 970 3.11 994 3.25 1017 3.40 1039 3.55 1061 3.70 1082.3 3.85
5000 892 2.97 920 3.15 946 3.33 971 3.50 996 3.68 1020 3.85 1043 4.02 1066 4.18 1088 4.35 1109.6 4.50
5500 922 3.49 949 3.70 975 3.90 999 4.09 1023 4.28 1047 4.48 1070 4.68 1091 4.87 1114 5.06 1135.6 5.24
6000 950 4.05 977 4.29 1002 4.51 1028 4.74 1052 4.96 1074 5.16 1098 5.38 1120 5.59
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 50.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table 51.
For Oversized Evaporator Fan Speed (RPM), reference Table 53.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 54 to determine additional static pressure drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
*For 2500, 3250 and 4000 CFM, unit applications below 320 CFM/Ton are only applicable to TCD models only (No Gas Heat). See below for restrictions.
Electric heaters restricted on applications below 320 CFM/Ton.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 320 CFM/Ton.