66 RT-PRC024-EN
Performance Data
(25 Tons High Efficiency)
Table 48. Evaporator Fan Performance 25 Tons TC*301C Standard Refrigeration or TXV System Downflow or Horizontal
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5-HP Standard Motor & Field Supplied Extra Low Static Drive 7.5-HP Standard Motor & Low Static Drive Accessory
5000* 576 1.56 606 1.71 635 1.88 663 2.05 690 2.22
6500* 576 2.11 601 2.27 625 2.43 649 2.59 674 2.78 698 2.97 722 3.18 746 3.38
7000* 579 2.32 608 2.54 633 2.73 656 2.89 678 3.06 700 3.25 723 3.44 745 3.65 768 3.87
7500* 582 2.59 611 2.78 640 3.02 665 3.24 687 3.43 708 3.61 729 3.79 749 3.98 770 4.19 792 4.41
8000 616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 739 4.22 759 4.41 778 4.60 797 4.81 817 5.03
8500 650 3.66 678 3.90 704 4.16 728 4.43 750 4.68 771 4.90 790 5.10 808 5.31 826 5.52 844 5.74
9000 685 4.31 712 4.56 737 4.83 760 5.12 782 5.39 802 5.65 821 5.88 839 6.09 856 6.30 873 6.53
9500 721 5.04 746 5.30 770 5.58 792 5.88 814 6.18 834 6.46 853 6.72 870 6.96 887 7.18 903 7.41
10000 756 5.85 780 6.12 803 6.41 825 6.72 846 7.04 866 7.35 884 7.64 902 7.90 918 8.14 934 8.38
10500 791 6.74 814 7.03 836 7.33 858 7.64 878 7.98 898 8.31 916 8.62
11000 827 7.71 849 8.02 870 8.33 891 8.63
7.5-HP Standard Motor & Drive 7.5-HP Standard Motor & High Static Drive Accessory
Continued
For Standard Evaporator Fan Speed (RPM), reference Table 50.
For Standard Motor & Low Static Drive Accessory Fan Speed
(RPM), reference Table 51.
For Oversized Evaporator Fan Speed (RPM), reference Table 53.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 54 to determine additional static pressure
drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the
full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
*For 5000, 6500, 7000 and 7500 CFM, unit applications below 320
CFM/Ton are only applicable to TCD models only (No Gas
Heat). See below for restrictions.
Electric heaters restricted on applications below 320 CFM/Ton.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and
Crankcase Heaters are required on applications below 320
CFM/Ton.
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5-HP Standard Motor & Drive
5000* 716 2.41 741 2.60 765 2.80 789 3.00 812 3.20
6500* 769 3.59 792 3.80 814 4.01 836 4.22 857 4.44
7000* 790 4.09 812 4.31 833 4.53 854 4.76 875 4.99
7500* 813 4.65 833 4.88 854 5.12 874 5.36 894 5.59
8000 837 5.26 857 5.51 876 5.76 896 6.01 915 6.26
8500 863 5.97 881 6.21 900 6.46 919 6.73 937 6.99
9000 890 6.76 908 7.00 925 7.25 943 7.52 961 7.79
9500 919 7.64 936 7.88 952 8.13 969 8.40 985 8.67
10000 949 8.62
10500
11000
7.5-HP Standard Motor & High Static Drive Accessory