RT-PRC024-EN 55
Performance Data
(12½ Tons High Efficiency)
Table 37. Evaporator Fan Performance 12½ Tons with Gas Heat YCH151C Standard Refrigeration System Horizontal
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive
(i)
(i)
Field Supplied Fan Sheave BK115 required. Field Supplied Belt may be necessary.
3-HP Standard Motor & Drive
4000 — — — — 520 1.01 550 1.13 580 1.25 610 1.38 638 1.51 666 1.65 693 1.80 720 1.95
4500 502 1.10 533 1.21 562 1.34 590 1.47 617 1.60 644 1.73 671 1.88 696 2.03 721 2.18 746 2.33
5000 551 1.47 579 1.61 606 1.74 632 1.87 657 2.02 682 2.17 706 2.31 730 2.46 754 2.63 777 2.80
5500 600 2.92 627 2.08 651 2.22 675 237 699 2.52 722 2.68 744 2.85 766 3.00 788 3.16 810 3.34
6000 649 2.46 675 2.64 698 2.79 720 2.94 742 3.11 764 3.28 785 3.46 805 3.64 825 3.81 845 3.98
5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive 3-HP Standard Motor & High Static Drive
4000 746 2.10 771 2.26 795 2.41 819 2.57 842 2.72 864 2.89 886 3.05 908 3.22 929 3.40 951 3.58
4500 770 2.49 794 2.66 818 2.83 841 3.01 863 3.18 885 3.35 906 3.53 927 3.70 947 3.88 967 4.06
5000 799 2.96 821 3.13 843 3.31 965 3.49 887 3.68 908 3.87 929 4.07 949 4.26 969 4.45 988 4.64
5500 831 3.52 852 3.70 873 3.89 893 4.07 913 4.26 933 4.46 953 4.66 972 4.87 992 5.08 1011 5.29
6000 865 4.15 885 4.35 905 4.55 924 4.75 943 4.95 962 5.15 980 5.35 999 5.56 — — — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 50.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table 51.
For Oversized Evaporator Fan Speed (RPM), reference Table 53.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 54 to determine additional static pressure drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.