70 RT-PRC024-EN
Performance Data
Table 55. Gas Fired Heating Capacities
Unit Model Heating Heating Air Temp.
Tons Number Input MBH
(i)
(i)
For two stage heaters (input or output), Second stage is total heating capacity. Second Stage/First Stage.
Output MBH
(ii)
(ii)
For two stage heaters (input or output), Second stage is total heating capacity. Second Stage/First Stage.
Rise, F
12½ YC*150D-L1, YC*151C-L1 150/100 122/81 10-40
YC*150D-H1,YC*151C-H1 250/175 203/142 25-55
15 YC*180B-L1 250/175 203/142 25-55
YC*180B-H1,YC*181C-H1 350/250 284/203 35-65
YC*181C-L1 250/175 203/142 15-45
17½ YC*210C-L1, YC*211C-L1 250/175 203/142 15-45
YC*210C-H1,YC*211C-H1 350/250 284/203 35-65
20 YC*240B-L1, YC*241C-L1 250/175 203/142 15-45
YC*240B-H1, YC*241C-H1 400/300 324/243 25-55
25 YC*300B-L1, YC*301C-L1 250/175 203/142 15-45
YC*300B-H1, YC*301C-H1 400/300 324/243 25-55
Table 56. Auxiliary Electric Heat Capacity
Total
(i)
(i)
Heaters are rated at 240v,380v,480v and 600v. For other than rated voltage, CAP= (voltage/rated voltage)
2
x rated cap.
Stage1 Stage 2
Unit Model kW MBH No. of kW MBH kW MBH
Tons Number. Input
(ii)
(ii)
For all input/output categories, does not include fan power or heat.
Output Stages Input Output Input Output
12½-15 TC*150D3,D4,DW,DK 18.00 61.47 1 18.00 61.47
TC*180B3,B4,BW,BK 27.00
(iii)
(iii)
27 kW heater can be used with TCD181C4, TCD211C4, TCD241C4 and TCD301C4 only. Cannot be used with oversized motor.
92.15 2 9.00 30.72 18.00 61.43
TC*151 or 181C3,C4,CW 36.00 122.94 2 18.00 61.47 18.00 61.47
54.00 184.41 2 36.00 122.94 18.00 61.47
17½, 20, 25 TC*210C3,C4,CW,CK 36.00 122.94 2 18.00 61.47 18.00 61.47
TC*240,300B3,B4,BW,BK 54.00 184.41 2 36.00 122.94 18.00 61.47
TC*211, 241, 301C3,C4,CW 72.00
(iv)
(iv)
Not available on TC*210C.
*Indicates both downflow and horizontal units.
245.88 2 36.00 122.94 36.00 122.94
Table 57. Electric Heater Voltage Correction Factors (Applicable to Auxiliary Heat Capacity)
Nominal Distribution Capacity
Voltage Voltage Multiplier
208 0.75
240 230 0.92
240 1.00
440 0.84
480 460 0.94
480 1.00
540 0.81
600 575 0.92
600 1.00