6 BAS-SVX17B-EN
Pre-Installation
This section provides the following pre-installation information:
Location considerations
Height requirements
Mounting surfaces
Recommended wire lengths
Location Considerations
Placement of the sensor is critical to proper operation. When selecting a location, avoid the
following:
Areas of direct sunlight
Areas in the direct airstream of air diffusers
Exterior walls and other walls that have a temperature differential between the two sides
Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys,
or other heat-generating equipment
Drafty areas
Dead spots behind doors, projection screens, or corners
Walls that are subject to high vibration
Areas with high humidity
High traffic areas (to reduce accidental damage or tampering)
Height Requirements
It is recommended that you mount the back plate a maximum distance of 54 inches above the floor.
If a parallel approach by a person in a wheelchair is required, reduce the maximum height to 48
inches.
Note: Consult section 4.27.3 of the 2002 ADA (Americans with Disability Act) guideline, and local
building codes, for further details regarding wheelchair requirements.
Mounting Surfaces
Using the hardware provided, mount the back plate to a flat surface such as sheetrock or plaster,
or an electrical junction box. The sensor must be mounted plumb for accurate temperature control
and to ensure proper air movement through the sensor.
If mounting onto sheetrock or plaster, use the plastic threaded anchors (pre-drilling holes is not
usually necessary) and the two M3.5 x 20 mm mounting screws.
For mounting onto an electrical junction box, use the two 6-32 x 3/4 in. screws.
If you are replacing a horizontally mounted sensor and need to cover an opening in the wall,
use the adapter kit (p/n BAYMTPL103A).