XT500C DELUXE PROGRAMMABLE HEAT-PUMP THERMOSTAT
69-1404
Pub. No. 18-HD25D2-2
Table 3. Installer Setup Options for the XT500C
(Continued)
.
(continued)
Press Time
or
Press Increase or Decrease to change setting
Installer
Factory Setting Other Choices
Actual
Select
Setup Number
Display Description Display Description
Setting
Em. Ht. cycle rate 7 5 55 cph recommended
3, 6, or 9 cph not
recommended
3, 6, or 9 33 cph
66 cph
99 cph
Stage 1 cooling
cycle rate
9333 cph recommended
2 or 5 cph not
recommended
2 or 5 22 cph
55 cph
Stage 2 cooling
cycle rate
10 3 33 cph recommended
2 or 5 cph not
recommended
2 or 5 22 cph
55 cph
System setting
adjustment
12 0 Auto changeover 1 or 2 1Manual
changeover
2Auto changeover
only
Adaptive
Intelligent
Recovery
control
13 0 Adaptive Intelligent
Recovery (a Honeywell
trademark) control is
activated (system starts
early so setpoint is
reached by start of
program period)
1 Conventional
recovery (system
starts recovery at
programmed time)
Degree temp -
erature display
14 0 Temperature displays
in °F
1 Temperature displays
in °C
Clock format 16 0 12-hour clock format 1 24-hour clock format
Extended fan
operation in
heating
a
19 0 No extended fan
operation after the call
for heat ends
1, 2 or 3 1Fan operation
extends 30 seconds
after the call ends.
2Fan operation
extends 60 seconds
after the call ends.
3 Fan operation
extends 90 seconds
after the call ends.
Extended fan
operation in
cooling
20 0 No extended fan
operation after the call
for cool ends
1, 2 or 3 1Fan operation
extends 30 seconds
after the call ends.
2Fan operation
extends 60 seconds
after the call ends.
3 Fan operation
extends 90 seconds
after the call ends.
Outdoor
temperature
display (select
models)
24 0 No outdoor temperature
displays
1 Outdoor temperature
displays. Requires a
TAYSENS100A
Outdoor Sensor.
Comfort-R
Enable
28 0 No fan delay 1 or 2 130 seconds
215 seconds